197thhhc , 212sparky , 2dogsafightin , 319 , AFowl , aiuduin , ammodude , AndyC , armytruck63 , backroads , bigmatt , bmod305 , Bob H , Bolkbich , boonedoggy , bubbahana , butch atkins , carter09 , Castle Bravo , cattlerepairman , Cgzmt , Chain-Saw , chess , Clayshootr , cornrichard , Csm Davis , cucv1833 , dbwillis , dellray , Detonation , dezert ratt , DieselBob , DieselInfantry711 , Dieselking22 , dirtroadoutlaw , dozer1 , dpsmith , Durango_USMC , Evil Dr. Porkchop , exbrown , Feelin_froggy , fordgasmz , G-Force , Goose2448 , gunboy1656 , guner51 , hdrigid70 , hippiedude , Hot Duck , Ironhorse , j3ffw23 , JB , jeepzilla47 , jets1959 , johnejones , jstorch , Katahdin , Kbike230 , keith648356 , Lapua Dan , m816 someday , mactiredearg , maddawg308 , Mator , maxpanic , michigandon , Monkey Man , moriboy , MT4222 , ODdave , onewoodsrider , paulrance , pcruz , pegasus55 , pooka , quickfarms , RAYZER , rebel_raider , RED HORSE , Repo3004 , rfjdarrin , Ridgerunner , robertss , Roboskid , RRworker , sandcobra164 , Scooteerr , sf38a1 , SGTskully , sharkhunter2018 , silverstate55 , SMOKEWAGON66 , steelandcanvas , Stonepicker1 , Superdave , tbanks , tennmogger , theHateTiger , tjmilitary , topo , USAFSS-ColdWarrior , uscgmatt , vtdeucedriver , WantOne , willy , wkbrdngsnw , woodwalker , youngunbd
Most users ever online was 902, 10-29-2011 at 04:09.
Reply
 
LinkBack Thread Tools

Old 11-09-2011, 09:31   #1 (permalink)
4 Star General
 
Boatcarpenter's Avatar
 
Join Date: Jul 2005
Location: Marlborough, NH
Posts: 1,870
Boatcarpenter is on a distinguished road
Default % Load on convenience outlets

If you plug into the convenience outlets, does the %load meter give you the % load for those outlets or the whole set?
BC
__________________
1970 M35a2 W/W Whistler Turbo NH Antique Tag MCB6
72 Triumph 650
1984 22' Sisu Lobster style cruiser 165HP 229CID Crusader
PETA=People Eating Tasty Animals
"Complexity is easy to create; simplicity is difficult."
The gene pool could use a little chlorine.
SS Member 1493
Boatcarpenter is offline   Reply With Quote
Old 11-09-2011, 09:38   #2 (permalink)
LDS power baby
 
gimpyrobb's Avatar
 
Join Date: Dec 2005
Location: cincy, Oh
Posts: 15,693
gimpyrobb will become famous soon enough
Default

The "CO" is only like 15amp. The % load is for the lugs.
gimpyrobb is offline   Reply With Quote
Old 11-09-2011, 12:52   #3 (permalink)
4 Star General
 
Boatcarpenter's Avatar
 
Join Date: Jul 2005
Location: Marlborough, NH
Posts: 1,870
Boatcarpenter is on a distinguished road
Default

Thanks Gimp. I forgot to mention the genset is a MEP002a.
BC
__________________
1970 M35a2 W/W Whistler Turbo NH Antique Tag MCB6
72 Triumph 650
1984 22' Sisu Lobster style cruiser 165HP 229CID Crusader
PETA=People Eating Tasty Animals
"Complexity is easy to create; simplicity is difficult."
The gene pool could use a little chlorine.
SS Member 1493
Boatcarpenter is offline   Reply With Quote
Old 11-09-2011, 15:21   #4 (permalink)
Colonel
 
Join Date: Nov 2010
Location: Louisiana
Posts: 250
Crawdaddy is on a distinguished road
Default

Doesn't matter if it's a MEP-002 or -003. The convenience outlet is for very low-powered use.
Crawdaddy is offline   Reply With Quote
Old 11-09-2011, 15:51   #5 (permalink)
4 Star General
 
Boatcarpenter's Avatar
 
Join Date: Jul 2005
Location: Marlborough, NH
Posts: 1,870
Boatcarpenter is on a distinguished road
Default

OK guys, here is the scoop.
Had some time to run a test today.
Wired a duplex outlet to my L3 and Lo.
Ran my nail gun compressor which is rated at 14 amps from the convenience outlet and the % load read about 25%, which is about correct for a 52 amp output unit.
Ran it on the duplex wired to the lugs and % load was exactly the same.
Compressor on cold start % load jumped to a little over 40%.
Warm startup a little under 30% load.

BC
__________________
1970 M35a2 W/W Whistler Turbo NH Antique Tag MCB6
72 Triumph 650
1984 22' Sisu Lobster style cruiser 165HP 229CID Crusader
PETA=People Eating Tasty Animals
"Complexity is easy to create; simplicity is difficult."
The gene pool could use a little chlorine.
SS Member 1493
Boatcarpenter is offline   Reply With Quote
Old 11-09-2011, 16:17   #6 (permalink)
3 Star General
 
Keith_J's Avatar
 
Join Date: Aug 2009
Location: San Antonio TX
Posts: 962
Keith_J is on a distinguished road
Default

Control transformer 1 (CT1) is what the % rated current meter is measuring. CT1 measures all windings, depending on position of S8.

NEVER run any load over 500 Watts, even though the circuit breaker is 15 amperes which will support a 1500 Watt load. Why? Because the outlets are driven by only one of the six windings. So even though the generator can put out 52 amperes at 120 volts, the outlet can only deliver 1/6th of that or 8-2/3 Amperes (8.66 amps).

When one winding is loaded, the control voltage transformer along with the voltage regulator boost field voltage to compensate. This causes the other unloaded windings to generate higher voltage which can break down insulation. Running 15 A off the outlets also heats the one loaded coil and thermal expansion conspires with the voltage stress to break down insulation.

When the windings are uniformly loaded, the heating is uniform and very little thermal stress happens.
Keith_J is offline   Reply With Quote
The Following 4 Users Say Thank You to Keith_J For This Useful Post:
Beerslayer (11-10-2011), RIrvin (11-09-2011), storeman (11-09-2011), treeguy (11-09-2011)
Old 11-09-2011, 18:46   #7 (permalink)
2 Star General
 
Join Date: Apr 2009
Location: SW, Louisiana
Posts: 650
Isaac-1 is on a distinguished road
Default

Keith, you keep saying this, and while I have not looked at the schematics for the MEP-002/003 I can't see how it can be true, since the tie points for all of the connection options for the output voltages would parallel at least 2 windings, meaning the minimum in 3 phase mode would be 1/3 not 1/6 of the output, which would be at least 1600 watts on a MEP-002. Electricity just does not behave the way you seem to be implying if does since it would flow through both the parallel windings even if the physical connection were to only one tie point.

Ike
Isaac-1 is offline   Reply With Quote
Old 11-09-2011, 19:03   #8 (permalink)
Sergeant Major
 
ETN550's Avatar
 
Join Date: Sep 2011
Location: Knoxville, TN
Posts: 145
ETN550 is on a distinguished road
Default

I'm not sure about the 002 / 003 but they do take the outlets off of one of six windings. This is a direct take off upstream of the reconnection switch. On the 016b which has three windings the outlets are taken off of winding #1, T1-T4. The interesting thing is that in the 120VAC single phase mode the tap points for the outlet are the same for L1 - L2 which is the whole rated load output. Therefore, it can be run up to the fuse limit. Note that in addition to the 120 outlets the same source is used to supply the frequency transducer and a transformer for the field supply.

I think there are some modes on the 002 / 003 where the #6 outlet winding is paralleled with another winding. In that case the outlet load can be safely doubled. In modes where the outlet winding is not in parallel with any other winding then it can handle only a small amount of power.

Lesson: Know how it is wired and do not exceed the winding capacity, but take advantage of parallel windings.
ETN550 is offline   Reply With Quote
Old 11-09-2011, 19:45   #9 (permalink)
General
 
storeman's Avatar
 
Join Date: Oct 2010
Location: Mathews County, VA
Posts: 502
storeman is on a distinguished road
Default

Soooooo. How does one determine parallel windings if they only occur on some models? I have 2 002a's and a "parts" 003a. How would I recognize parallel or not?
Jerry
__________________
M101A3
MEP-002A 10 on hand!
Two to keep, 2 ready to sell.
Two being worked on.
Four being parted out.

See classifieds for huge generator parts listing
jerry@queenscreek.com


storeman is offline   Reply With Quote
Old 11-10-2011, 18:50   #10 (permalink)
Sergeant Major
 
ETN550's Avatar
 
Join Date: Sep 2011
Location: Knoxville, TN
Posts: 145
ETN550 is on a distinguished road
Default

Quote:
Originally Posted by storeman View Post
Soooooo. How does one determine parallel windings if they only occur on some models? I have 2 002a's and a "parts" 003a. How would I recognize parallel or not?
Jerry
Hi Jerry,

Got to look in your manuals for the connection diagrams. Not the big complicated wiring diagrams. Usually where the manual talks about which output lugs to use for the selected voltage and phase. They depict the windings like zig zag lines and show them arranged in a triangle fashion or laid out in a line. I thought someone posted some diagrams for your gen on here not too long ago. Any 002 owners got one handy??
ETN550 is offline   Reply With Quote
Reply

Thread Tools

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is Off
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
Mep 002a output in amps / %rated current meter RWG421 Auxiliary Equipment 7 11-05-2011 23:41
How does your Voltmeter read under load? shkira CUCV 19 08-20-2011 12:28
Load test of an MEP006a sewerzuk Auxiliary Equipment 3 07-25-2011 00:33
help please with diesel generator add-on advice OPCOM Deuce Modification and Hot-Rodding 104 10-29-2007 21:04
generator testing and wet-stacking OPCOM Auxiliary Equipment 3 01-23-2007 19:45

Powered by vBadvanced CMPS v3.2.2

All times are GMT -4. The time now is 22:52.


Copyright 1999-2012 SteelSoldiers.Com No information or photos to be used without permission.