197thhhc , 212sparky , 2buells , 2ndchance , 319 , 5tontiny , AFowl , AndyC , armytruck63 , backroads , Barney-the-Duece , big hoss , bmod305 , Bolkbich , boonedoggy , butch atkins , Cgzmt , Chain-Saw , chess , chevyCUCV , chief mark , chvss65 , Clayshootr , clinto , Condec , Csm Davis , cucv1833 , Danger Ranger , dellray , Detonation , dezert ratt , DieselBob , DieselInfantry711 , Dieselking22 , dozer1 , DUG , Durango_USMC , Evil Dr. Porkchop , exbrown , Feelin_froggy , finnd1 , G-Force , gunboy1656 , guner51 , hdrigid70 , hippiedude , hndrsonj , Ironhorse , j3ffw23 , jets1959 , johnejones , joshjourdan , jstorch , jw4x4 , Katahdin , Kbike230 , keith648356 , Lapua Dan , m816 someday , mactiredearg , maddawg308 , Mator , maxpanic , mikew , Monkeyboyarmy , moriboy , MT4222 , NDT , ODdave , onewoodsrider , paulrance , pcruz , pegasus55 , quickfarms , RAYZER , rebel_raider , Repo3004 , rfjdarrin , robertss , Roboskid , RRworker , Scooteerr , sf38a1 , SGTskully , sharkhunter2018 , silverstate55 , SMOKEWAGON66 , steelandcanvas , Stonepicker1 , Superdave , tennmogger , topo , uscgmatt , vtdeucedriver , WantOne , willy , wkbrdngsnw
Most users ever online was 902, 10-29-2011 at 04:09.
Reply
 
LinkBack Thread Tools

Old 11-28-2011, 12:34   #1 (permalink)
Colonel
 
sewerzuk's Avatar
 
Join Date: Mar 2010
Location: Seaside, OR
Posts: 349
sewerzuk is on a distinguished road
Default re-wiring my MEP-004a for different voltages, including single phase

So…most of us with 3 phase MEP generator sets have wondered if it is possible to rewire the set for something other than 120/208 or 240/417v. Some have asked the question in the forum here and the consensus seems to be that it won’t work. I think it will.

*I am using one of my MEP-004a’s for testing, so the numbers I am posting are related to its power/current/voltage ratings.

Why re-configure? Well, many of the people who own these generators use them only in single phase, at 120/208v. According to the TM, this is permissible, and the vast majority of 240v appliances operate just fine at 208v. But…there are a few loads that don’t like 208v. And, you are limited to 100% of rated current for each phase; so unless you are sending power to 2 separate services, you can only get about 43A, or 9kW. Re-configuring the set for its intended use nets you more useable power, and provides more appropriate voltage for the loads.

I began thinking about the possibility of re-configuring my MEP-004a the other day, and spent a few hours reading through Steelsoldiers and Smokstak; although there were a few stories of a guy who knew a guy whose buddy’s brother-in-law rewired an MEP for single phase, I couldn’t find a single post by somebody who had actually attempted it. I went a step further, and wondered if it would be possible to wire the generator in a 3 phase delta configuration, thinking that 120/240 delta would be useful for the small shop with several large 240v 3 phase loads, and a requirement for a light single phase 120v load. So, I spent another few hours poring over the schematics. Here are the conclusions I come up with:

The MEP’s use a standard 12 lead generator head. That means that, from the generator’s point of view, pretty much any standard voltage is possible. The problem is in the generators instrumentation and control system…the current transformers for the ammeter and safety trips are designed around a 3 phase wye setup. There is no provision for single phase in how the CT’s are wired. However…this doesn’t mean that single phase isn’t possible, it just means that there might be a few “quirks” to deal with when running single phase. I think that all of the safety trips will still function properly, as they are all designed around current passing through the individual windings of the generator. It doesn’t matter how the load is placed on those windings…the cumulative current is what is important and that will not change. The wattmeter should work properly. I believe that the voltmeter will also work properly; it will indicate line voltage as designed and simply read 0 when switched to the phase not being used (for single phase). The ammeter should also indicate current…however it may be a little confusing. It may indicate actual line current, ½ line current, or 1/√3 line current depending on how the switch is selected and the method I choose to re-wire the generator. This is because of where the CT measures the current (it may be possible to re-wind the CT to work properly, but I’ll jump that hurdle if my re-wire actually works and produces useable power). The voltage regulator should also work properly; it is designed to provide 120v per winding and that is all that is needed to produce the voltages that I am aiming for. 480v 3 phase delta is not possible with this generator, as it requires 240v per winding. I believe the following configurations are possible:

3 phase:
1. 417/240v wye (adjustable from 348/200v up to 480/277v) This is a factory-installed voltage
2. 208/120v wye (adjustable from 173/110v up to 240/138v) This is a factory-installed voltage
3. 240/120v Delta (adjustable from 200/100v up to 277/138v) This does change how current flows through the CT’s and may cause problems with the overload trip and ammeter reading
4. 120v Delta (adjustable from 100v to 138v) I don’t think this is a very useful configuration…don’t know of too many 120v 3 phase loads. But, it should be possible. Same CT issues as 240/120v delta.

Single Phase (both 120/240v configurations produce the same power, just different methods of wiring):
1. 120/240v Double Delta (adjustable from 100/200v up to 138/277v) Same issues with the CT
2. 120/240v low zigzag, or dogleg (adjustable from 100/200v up to 138/277v) Same issues with the CT
3. 240/480v high zigzag (adjustable from 200/400v up to 277/554v) Don’t know how many single phase 480v loads are out there, but 554v might be useful for the guy trying to get a little more lightning length out of his Tesla coil. Same issues with the CT

There are a few issues to deal with and things to think about:
1. The cable size going to the main circuit breaker and to the load terminals is too small for the increased current that is possible during single phase operation. It should be upsized appropriately.
2. I believe that no additional current would be traveling through individual generator windings, meaning that you could get the full rated 15kW out of the generator at 120/240v single phase without exceeding the design limits of the windings (however, the overload trip will still limit you to the current ratings from 3 phase operation).
3. The CT 1-3 could be re-wound to indicate proper current on each “leg”. This would also affect the overload trip.
4. Re-winding the CT’s might indicate proper current; however the overload trip is still set to 130% of the 3 phase rated current; meaning that it will still trip at roughly 55A, even though 63A would be the 100% rated current for single phase 120/240. It may be possible to add a properly sized resistor inline with the overload trip relays, as they only have a very small amount of current passing through them. This resistor could be sized to adjust the overload trip to the new 130% rated current of 82A. Another option would be to increase the size of resistors R23, R24, and R25 in the tactical relay box. It also may be possible to remove one turn of the generator leads from the CT; this would change how the ammeter and wattmeter read, and it would also raise the overload trip setpoint by roughly 25% (this is the method I intend to experiment with).
5. L0 is internally bonded to ground in the generator; therefore it would be absolutely critical to remove this bond prior to starting up the generator in delta configuration. Failure to do so would result in a hardwired phase to ground short.
6. T10, T11, and T12 are bonded together under the voltage reconnection board. It is critical to remove/modify this bonding bar for any configuration other than Wye. Failure to remove it would result is a phase to phase to phase short.
7. The generator reconfiguration should be able to be completed all on the voltage reconnection board; a few jumper wires and buss bars would complete the reconfiguration. I’m hoping to come up with a VERY simple reconnection for zigzag; the other connections will require a bit more work. For that reason I’ll try the zigzag first, and if it works I may proceed to experiment with the delta configurations.

I am planning on attempting this in the coming few weeks with one of my -004a sets. Of course I’ll take all of the safety precautions; and I am prepared for the possibility that I may destroy some critical internal components with my meddling (although I don’t think this will happen…otherwise I wouldn’t be trying it).
I’ll set up the video camera when I first fire this thing up, just in case I manage to create molten copper and smoke instead of single phase power.
I think I have a grasp on the problems, pitfalls, etc. associated with this reconfiguration (albeit a loose grasp). I’m looking for input before I try this out…anything I’ve missed? Am I re-creating something that somebody else has already accomplished?

Attached some relevant schematics and diagrams...

edit 1: low zigzag re-configuration is complete; it works mostly as predicted. Details and a video on page 3
edit 2: additional reconnections have been made to correct issues with the installed voltmeter and voltage regulator. Details on page 4
edit 3: I plan to post the entire reconnection process here in this original post once all of the testing is complete
edit 4: here is the completed process:

http://www.youtube.com/watch?v=YmF4Awr3uc4
Attached Images
File Type: jpg 3 phase connection diagram.jpg (80.9 KB, 47 views)
File Type: jpg single phase connection diagram.JPG (61.9 KB, 46 views)
File Type: jpg generator schematic 1.jpg (102.6 KB, 47 views)
File Type: jpg generator schematic 2.jpg (68.0 KB, 47 views)
File Type: jpg generator schematic 3.jpg (54.3 KB, 40 views)
__________________
71 M35A2: 395's, flatbed, LED lighting, water/meth injection, full hydro, etc.
01 Dodge Ram 5.9: Fast. Real fast.
90 Samurai: onboard air, toyota PS, lockers, 6.5 tcase, Warn 9.5XP etc.
00 Vitara: Unimog 404 axles, air lockers, 4 link, full hydro, W56 tranny, dual cases, 40" pitbull rockers with Stauns, work in progress
01 XJ: Ford 8.8" w/ Ected locker, lock right front, 4.56 gears, SYE kit, custom bumpers, sliders, onboard air, etc.
Lots of MEP's
One very understanding wife

Last edited by sewerzuk; 02-01-2012 at 19:03.
sewerzuk is offline   Reply With Quote
The Following User Says Thank You to sewerzuk For This Useful Post:
OPCOM (12-10-2011)
Old 11-28-2011, 13:25   #2 (permalink)
Corporal
 
Join Date: May 2011
Location: Upstate, NY, USA
Posts: 28
aczlan is on a distinguished road
Default

Sounds interesting. Am I reading correctly that this would be possible to do to a 002 or 003 as well?

Aaron Z
aczlan is offline   Reply With Quote
Old 11-28-2011, 13:49   #3 (permalink)
Colonel
 
sewerzuk's Avatar
 
Join Date: Mar 2010
Location: Seaside, OR
Posts: 349
sewerzuk is on a distinguished road
Default

Quote:
Originally Posted by aczlan View Post
Sounds interesting. Am I reading correctly that this would be possible to do to a 002 or 003 as well?

Aaron Z
-002's and -003's have a built in switch that allows 120/240 double delta, 120v single phase, or 208/120v 3 phase wye. The re-configuration for these would be more complicated, as all 12 leads go to that enormous switch.

My plan would work well for an MEP-004, -005, or -006 and their precise equivalents because they all use the same voltage reconnection board.
__________________
71 M35A2: 395's, flatbed, LED lighting, water/meth injection, full hydro, etc.
01 Dodge Ram 5.9: Fast. Real fast.
90 Samurai: onboard air, toyota PS, lockers, 6.5 tcase, Warn 9.5XP etc.
00 Vitara: Unimog 404 axles, air lockers, 4 link, full hydro, W56 tranny, dual cases, 40" pitbull rockers with Stauns, work in progress
01 XJ: Ford 8.8" w/ Ected locker, lock right front, 4.56 gears, SYE kit, custom bumpers, sliders, onboard air, etc.
Lots of MEP's
One very understanding wife
sewerzuk is offline   Reply With Quote
Old 11-28-2011, 17:33   #4 (permalink)
General
 
PeterD's Avatar
 
Join Date: Dec 2009
Location: Jaffrey, NH
Posts: 419
PeterD is on a distinguished road
Default

I intend to watch this project closely... I wish I lived closer to you, I'd be over in a flash to help out!
__________________
My name is Peter (AKA NEHOG), and I'm never going to grow up.

(And I can't read *p o s t s* easily because of the lack of contrast between the letters and the background!)

http://www.pmdcooler.com - Order your cooler online!

AM General H1 NA Wagon (95)
AM General H1 Turbo Wagon (99)
Dodge Ram 2500 Hemi
MEP-004AAN with M200A1
PeterD is offline   Reply With Quote
Old 11-28-2011, 18:46   #5 (permalink)
General
 
storeman's Avatar
 
Join Date: Oct 2010
Location: Mathews County, VA
Posts: 502
storeman is on a distinguished road
Default

Peter,
Not to call you out.......But as I recall, you use MEP-004a single phase routinely as your backup power and I would love to know how and what amps you get from yours. This is an interesting thread. I turned down a mint 004a at Richmond last year because I was afraid of it.
Jerry
__________________
M101A3
MEP-002A 10 on hand!
Two to keep, 2 ready to sell.
Two being worked on.
Four being parted out.

See classifieds for huge generator parts listing
jerry@queenscreek.com


storeman is offline   Reply With Quote
Old 11-28-2011, 19:09   #6 (permalink)
4 Star General
 
Stonepicker1's Avatar
 
Join Date: Nov 2008
Location: Coconut Creek, Florida
Posts: 1,251
Stonepicker1 is on a distinguished road
Default

I'll be watching this project also. Good luck.
If it works, I might keep my 30kw.
__________________
Phil
1SG 88Z5M/63Z /63B/52D

1986 Chevy M1031 into M1028A1 in 1992
1984 M1009
1991 MEP-003, 10 KW Gen
2006 PU-405, 30KW Gen
2006 M116A3 1 ton Gen Trl (2ea)
1999 CUCV-II 6.5L Turbo(New 6.5 GEP engine)
2000 CUCV-II CREW CAB, 6.5L Turbo
1986 Chevy M1028A2 Dually(New 6.5L GEP engine w/Banks Turbo)
1986 Chevy M1028A2 Dually, 6.2L
1984 M923A1, 5 TON CARGO, Dropside(waiting on ECU to clear)
1984 M923, 5 TON, CARGO, 6X6 (ex-USMC)
VFW Life Member (Hillsdale, MI)
Stonepicker1 is online now   Reply With Quote
Old 11-28-2011, 19:21   #7 (permalink)
Colonel
 
sewerzuk's Avatar
 
Join Date: Mar 2010
Location: Seaside, OR
Posts: 349
sewerzuk is on a distinguished road
Default

Quote:
Originally Posted by storeman View Post
Peter,
Not to call you out.......But as I recall, you use MEP-004a single phase routinely as your backup power and I would love to know how and what amps you get from yours. This is an interesting thread. I turned down a mint 004a at Richmond last year because I was afraid of it.
Jerry
Edit: oops! Just realized that question wasn't directed at me...but I'm sure he's doing the same 120/208 setup I am. Dang small screen on my phone!

Hey...no problem. It's a legit question!

Yep...I have an -004 for backup power for my house and shop. I just pull 120/208 off of 2 separate phases and send one to the house, and the other to my shop. I have a 200 amp transfer switch at each meter base to transfer over the entire service. 100% rated current for each phase is about 46 amps, and the overloads trip after about 8 minutes at 130% rated current, or about 60 amps. so, I can get 60 amps sustained to each building indefinitely, at 120/208 single phase. This runs everything in my house, an 90 % of the equipment in my shop. Every 240v load I have works fine on 208 (although my dryer takes a little longer to dry a load of laundry). It works great for my situation, but most people don't need to feed 2 separate electrical services, so they're stuck with a little less than 10kw.

If you're interested, I have a YouTube video showing one of my 004's powering my shop single phase. In the video, I start several large loads on the generator, and even show the waveform with my oscilloscope. I'd post a link to it, but I'm sending this from my phone and don't have the url handy. Just search through my YouTube videos (my name is the same there as it is here; sewerzuk)

edit: here it is: http://www.youtube.com/watch?v=I_ykrzMbTZk
__________________
71 M35A2: 395's, flatbed, LED lighting, water/meth injection, full hydro, etc.
01 Dodge Ram 5.9: Fast. Real fast.
90 Samurai: onboard air, toyota PS, lockers, 6.5 tcase, Warn 9.5XP etc.
00 Vitara: Unimog 404 axles, air lockers, 4 link, full hydro, W56 tranny, dual cases, 40" pitbull rockers with Stauns, work in progress
01 XJ: Ford 8.8" w/ Ected locker, lock right front, 4.56 gears, SYE kit, custom bumpers, sliders, onboard air, etc.
Lots of MEP's
One very understanding wife

Last edited by sewerzuk; 11-28-2011 at 20:54.
sewerzuk is offline   Reply With Quote
Old 11-28-2011, 20:20   #8 (permalink)
General
 
storeman's Avatar
 
Join Date: Oct 2010
Location: Mathews County, VA
Posts: 502
storeman is on a distinguished road
Default

sewerzuk
now i begin to understand your goal (after re-reading your original post) I guess balanced load is key to keep the unit from burning up. Can you run indefinitely on 120 single phase? FROM THAT SINGLE PHASE OPERATION CAN YOU GET 2 LEGS TO FEED A 220/240v BREAKER ON A NORMAL HOUSE WIRING SYSTEM?
opps, didn't realize i was typing in caps.
Jerry
__________________
M101A3
MEP-002A 10 on hand!
Two to keep, 2 ready to sell.
Two being worked on.
Four being parted out.

See classifieds for huge generator parts listing
jerry@queenscreek.com


storeman is offline   Reply With Quote
Old 11-28-2011, 20:37   #9 (permalink)
Colonel
 
Join Date: Mar 2009
Location: Williamsburg VA
Posts: 338
Ken_86gt is on a distinguished road
Default

I know that you can setup the MEP-005 and MEP-006 to single phase 120/240. I did this with my MEP-005 as a test and it worked for me. I don't know if the MEP-004 has the same generator head. I had posted a link to this page some time ago, it may help you:
Re-wiring a three phase generator | AnOldMan.com

When I did mine, I had some stange meter readings on the gen set, but confirmed with a hand held meter.
Ken_86gt is offline   Reply With Quote
Old 11-28-2011, 20:51   #10 (permalink)
Colonel
 
sewerzuk's Avatar
 
Join Date: Mar 2010
Location: Seaside, OR
Posts: 349
sewerzuk is on a distinguished road
Default

Quote:
Originally Posted by storeman View Post
sewerzuk
now i begin to understand your goal (after re-reading your original post) I guess balanced load is key to keep the unit from burning up. Can you run indefinitely on 120 single phase? FROM THAT SINGLE PHASE OPERATION CAN YOU GET 2 LEGS TO FEED A 220/240v BREAKER ON A NORMAL HOUSE WIRING SYSTEM?
opps, didn't realize i was typing in caps.
Jerry
Yep; my plan is to get 100% of the generator's rated output from L1 and L3 at 120/240v; same as common residential service. This also allows you to get 240v, instead of 208.

Quote:
Originally Posted by Ken_86gt View Post
I know that you can setup the MEP-005 and MEP-006 to single phase 120/240. I did this with my MEP-005 as a test and it worked for me. I don't know if the MEP-004 has the same generator head. I had posted a link to this page some time ago, it may help you:
Re-wiring a three phase generator | AnOldMan.com

When I did mine, I had some stange meter readings on the gen set, but confirmed with a hand held meter.
Wow...missed that one during my searches! The author of that web page did EXACTLY what I was planning to do, with reference to the low zigzag wiring. At least I can fire mine up now without worrying about wearing my firefighting gear

He accomplished the proper output voltage, but still had to live with the reduced output because of the overload trip setpoint, and the funny meter readings. I intend to solve and/or explain those issues with my conversion.

I'll get right to doing a "how to" video for the -004 and -005. I'll post it up here as soon as I'm done...
__________________
71 M35A2: 395's, flatbed, LED lighting, water/meth injection, full hydro, etc.
01 Dodge Ram 5.9: Fast. Real fast.
90 Samurai: onboard air, toyota PS, lockers, 6.5 tcase, Warn 9.5XP etc.
00 Vitara: Unimog 404 axles, air lockers, 4 link, full hydro, W56 tranny, dual cases, 40" pitbull rockers with Stauns, work in progress
01 XJ: Ford 8.8" w/ Ected locker, lock right front, 4.56 gears, SYE kit, custom bumpers, sliders, onboard air, etc.
Lots of MEP's
One very understanding wife

Last edited by sewerzuk; 12-09-2011 at 01:24.
sewerzuk is offline   Reply With Quote
Reply

Thread Tools

Posting Rules
You may not post new threads
You may not post replies
You may not post attachments
You may not edit your posts

BB code is On
Smilies are On
[IMG] code is Off
HTML code is Off
Trackbacks are On
Pingbacks are On
Refbacks are On


Similar Threads
Thread Thread Starter Forum Replies Last Post
rewiring MEP004 for single phase FREDS Auxiliary Equipment 40 09-28-2010 13:45
MEP 002 Auction Price Grove Auxiliary Equipment 5 07-27-2009 15:44
15K Diesel Gen set 2deuce Auxiliary Equipment 14 11-29-2007 13:01
Tail Light Wiring Conversion/Problem... ems4ty Electrical 3 08-02-2007 12:46

Powered by vBadvanced CMPS v3.2.2

All times are GMT -4. The time now is 22:59.


Copyright 1999-2012 SteelSoldiers.Com No information or photos to be used without permission.