Tab Content
  • peapvp's Avatar
    Yesterday, 19:50
    peapvp replied to a thread MEP-004A, No output in Generators
    Ok, here is my very first Post and Video I posted on SS on 12.08.2013 of Paralleling Genset's like the 002A and 003A and this should be of...
    351 replies | 3877 view(s)
  • peapvp's Avatar
    Yesterday, 19:39
    Back by popular demand. I had inadvertently made changes to my YouTube channel and deleted the 4 videos This is the original Video Part 1 posted...
    18 replies | 1009 view(s)
  • peapvp's Avatar
    Yesterday, 18:54
    peapvp replied to a thread MEP-004A, No output in Generators
    That is possible as I did not check your current wiring. This transformer has the start and end reversed on H from the previous 100VA T2
    351 replies | 3877 view(s)
  • peapvp's Avatar
    Yesterday, 18:53
    peapvp replied to a thread MEP-004A, No output in Generators
    Yes that is Terminal #3 and #4 not X3 and X4! Just to make sure
    351 replies | 3877 view(s)
  • peapvp's Avatar
    Yesterday, 17:30
    peapvp replied to a thread MEP-004A, No output in Generators
    Thanks, 12.9 Ohm between #2 and #6 is your H Side
    351 replies | 3877 view(s)
  • peapvp's Avatar
    Yesterday, 17:28
    peapvp replied to a thread MEP-004A, No output in Generators
    X1=X1 = #2 X2=X2 = #4 ____X3 = #3 X3=X4 = #5 H1=H1 = #2 H2=H4 = #6 The old T2 had only 5 Terminals, new ones have 8 Terminals, hence the...
    351 replies | 3877 view(s)
  • peapvp's Avatar
    Yesterday, 17:17
    peapvp replied to a thread MEP-004A, No output in Generators
    Kris, the reason why I asked this question is because I don't know anything about your DMM.... My DMM displays O.F when nothing is connected to...
    351 replies | 3877 view(s)
  • peapvp's Avatar
    Yesterday, 16:59
    peapvp replied to a thread MEP-004A, No output in Generators
    is the 0.L on your DMM the Infinite Ohm / Resistance?
    351 replies | 3877 view(s)
  • peapvp's Avatar
    Yesterday, 16:49
    peapvp replied to a thread MEP-004A, No output in Generators
    Don't Rely, Verify!
    351 replies | 3877 view(s)
  • peapvp's Avatar
    Yesterday, 16:34
    peapvp replied to a thread MEP-004A, No output in Generators
    Curios to see the pictures when installed in the A11 - is it smaller/bigger/heavier/lighter then the original T2?
    351 replies | 3877 view(s)
  • peapvp's Avatar
    Yesterday, 16:33
    peapvp replied to a thread MEP-004A, No output in Generators
    Use the Ohmmeter......
    351 replies | 3877 view(s)
  • peapvp's Avatar
    Yesterday, 16:20
    peapvp replied to a thread MEP-004A, No output in Generators
    Follow the numbers - make sure you don't get H and X Side mixed up - the spacing between terminals is different - look very carefully at drawing and...
    351 replies | 3877 view(s)
  • peapvp's Avatar
    Yesterday, 15:41
    peapvp replied to a thread MEP-004A, No output in Generators
    Kris, I got the wiring diagram on my Laptop but it is also posted here already as Post #281 POST #281 Peter
    351 replies | 3877 view(s)
  • peapvp's Avatar
    Yesterday, 12:00
    peapvp replied to a thread MEP-004A, No output in Generators
    If you remove the Governor LMU A8 then you will loose the Reverse Power Protection Relay K15 - this affects only parallel operations of the Genset....
    351 replies | 3877 view(s)
  • peapvp's Avatar
    Yesterday, 09:56
    peapvp replied to a thread MEP-004A, No output in Generators
    For simplification purposes, here are the standard Generator Coil Configurations for 3 Phase Systems in this system you will get: T7 / L0 = 120...
    351 replies | 3877 view(s)
  • peapvp's Avatar
    Yesterday, 08:38
    peapvp replied to a thread MEP-004A, No output in Generators
    Guy, T7, T8, T9 will be the center tap connection when the reconnection board is moved to 400 - so they will be getting only 120 in this case ...
    351 replies | 3877 view(s)
  • peapvp's Avatar
    09-16-2019, 20:29
    peapvp replied to a thread MEP-004A, No output in Generators
    I also updated the A11 Schematic and added the Voltage Adjust Rheostat R2 on the front panel and how it is connected to the Voltage reconnection board
    351 replies | 3877 view(s)
  • peapvp's Avatar
    09-16-2019, 20:22
    peapvp replied to a thread MEP-004A, No output in Generators
    For anyone who doesn't know on where the Governor LMU A8 is located or what it looks like I attached the pic of it from Kris's 004A Utility Version...
    351 replies | 3877 view(s)
  • peapvp's Avatar
    09-16-2019, 20:03
    peapvp replied to a thread MEP-004A, No output in Generators
    Brian, thanks, like I said in post #300 that Sewerzuk's mod is in between 120 single and 120/208 single but it's really neither one. The...
    351 replies | 3877 view(s)
  • peapvp's Avatar
    09-16-2019, 17:40
    peapvp replied to a thread MEP-004A, No output in Generators
    Kris, You could also mount a 208/240VAC Panel light in parallel to the Fuse, this way if the Fuse goes out the Light comes On Peter
    351 replies | 3877 view(s)
  • peapvp's Avatar
    09-16-2019, 17:38
    peapvp replied to a thread MEP-004A, No output in Generators
    Brian, Thank You! You sure did it correctly. 126.9VAC across is exactly what I expected with output set to 125VAC because of the drop of about...
    351 replies | 3877 view(s)
  • peapvp's Avatar
    09-16-2019, 12:55
    peapvp replied to a thread MEP-004A, No output in Generators
    Kris, thank you. Something we could ad for few bucks. Brian, I forgot, that was the 3 Amp Fuse which blew when you tested the other VR...
    351 replies | 3877 view(s)
  • peapvp's Avatar
    09-16-2019, 11:19
    peapvp replied to a thread MEP-004A, No output in Generators
    Brian, that may have been the fuse which blew when you tested the VR with the bad SCR's and you told us that the fuse blew. Peter (PEAPVP)
    351 replies | 3877 view(s)
  • peapvp's Avatar
    09-15-2019, 11:20
    peapvp replied to a thread MEP-004A, No output in Generators
    This would be the necessary mods for 120/240 to work WARNING: However each generator coil T number has to be double checked and this is extremely...
    351 replies | 3877 view(s)
  • peapvp's Avatar
    09-15-2019, 09:40
    peapvp replied to a thread MEP-004A, No output in Generators
    Here is the Connection Diagram for the 002A/003A to switch between single phase 120, single phase 120/240 and three phase 120/208 As you can see,...
    351 replies | 3877 view(s)
  • peapvp's Avatar
    09-15-2019, 01:18
    peapvp replied to a thread MEP-004A, No output in Generators
    Brian, No problem. If you did the mod exactly per Sewerzuks Video then you got 208 on T2 H1 / H2 If you didn't move the X8HH wire which connects...
    351 replies | 3877 view(s)
  • peapvp's Avatar
    09-14-2019, 22:31
    peapvp replied to a thread MEP-004A, No output in Generators
    Brian, on the second VR the switch timing is off, hence the lower DC on R/S - a cap going bad.... on the other hand, 123 VAC on X1 / X3...
    351 replies | 3877 view(s)
  • peapvp's Avatar
    09-14-2019, 21:59
    peapvp replied to a thread MEP-004A, No output in Generators
    Brian, Thank You. I meant testing while the A11 is installed in the genset and genset running Peter
    351 replies | 3877 view(s)
  • peapvp's Avatar
    09-14-2019, 20:51
    peapvp replied to a thread MEP-004A, No output in Generators
    Brian, Thank You! The very last test I would like to know/perform: With the Genset set to 120/208 on the reconnection board and A11...
    351 replies | 3877 view(s)
  • peapvp's Avatar
    09-14-2019, 19:59
    peapvp replied to a thread MEP-004A, No output in Generators
    Brian, Thank you. If I understand you correctly then the A11 assembly you normally use has 50.7VDC which understandable moves the 125VAC point of...
    351 replies | 3877 view(s)
More Activity
About peapvp

Basic Information

Age
51
About peapvp
Location:
Basehor, KS
Interests:
MEP Gensets
Occupation:
Electrical Engineer

Signature


Peter
INOVA HIGHTECH Ltd.
Cage Code 6ZJM5

MEP 0xx and 8xx Auto / Remote Start Kits - THE ORIGINAL - since 2013!

Thank you for being a Customer!

Statistics


Total Posts
Total Posts
212
Posts Per Day
0.10
Total Thanks
Total Thanks
144
General Information
Last Activity
Yesterday 23:20
Join Date
10-08-2013
Referrals
0
Home Page
http://inovahightech.com
iTrader Profile Recent Ratings
Feedback Score:
Positive Feedback:
1
100.0%
Members who left positive:
Members who left negative:
1
0
Total positive feedback: 1
Submit Feedback For peapvp
View Complete Feedbacks for peapvp
  Past
Month
Past
6 Months
Past
12 Months
  0 0 0
  0 0 0
  0 0 0