• Steel Soldiers now has a few new forums, read more about it at: New Munitions Forums!

  • Microsoft MSN, Live, Hotmail, Outlook email users may not be receiving emails. We are working to resolve this issue. Please add support@steelsoldiers.com to your trusted contacts.

Search results

  1. CallMeColt

    MEP 803A Overload Fault Troubleshooting

    So, took me a bit to come back! Over the weekend I went to do my standard 6 hour load bank test & it failed. Had to work through some mechanical issues. Had the day off to go pickup an auction win & seems like it will pass today. At ~5hrs, 12,000 watt load. Needless to say, the issue this...
  2. CallMeColt

    MEP 803A Overload Fault Troubleshooting

    Replaced R13. Removed it & it was open. Getting a ~3.3 ohms at CT1/CT2. It's late, so tomorrow after work I will get it under load again.
  3. CallMeColt

    MEP 803A Overload Fault Troubleshooting

    Did this just now & got ~7.8 ohms. So, something is keeping them from parallel between CT1/2 & the resistors or one is bad. Looks like I know where to dig into next. Thank you!
  4. CallMeColt

    MEP 803A Overload Fault Troubleshooting

    I also wanted to upload this picture to make sure there is not something here that I'm missing that is out of place.
  5. CallMeColt

    MEP 803A Overload Fault Troubleshooting

    @kloppk R13 & R12 are getting the same, elevated voltage readings as I posted above. So, this is making me think there is an issue with the CT or the wire trail going through CT3 that is making the CT read higher? If I recall, the TM test for the CT in the machine is a simple continuity test &...
  6. CallMeColt

    MEP 803A Overload Fault Troubleshooting

    Okay, thank you. I don't know why I didn't check it. I must have read incorrectly in another post where you talked about this and thought only the first 3 were for each leg. This is what happens when brain fatigue sets in!
  7. CallMeColt

    MEP 803A Overload Fault Troubleshooting

    I did not take a measurement of R13. Good catch. Your diagram shows this & I kind of ignored it for some reason. I will have to pull the trailer back up to the shop & set the load bank up again to test. This afternoon I moved onto my M4K with about the same results as the generator. Should have...
  8. CallMeColt

    MEP 803A Overload Fault Troubleshooting

    Added a few things to my original post that I forgot to put in there. Also, After letting the contact cleaner dry & touching/tracing each wire to confirm it is in the proper place, no luck. I also unbolted to CT to make sure I could get a good look at the side of the S8 & some of those...
  9. CallMeColt

    MEP 803A Overload Fault Troubleshooting

    The load has nothing to do with it. It is a fault in the way it is sensing. The generator is working fine. If you set S6 for 3 phase, it is monitoring for such, it is not setting the generator to make 3 phase power. You set the way the generator makes power with S8. You set how the generator...
  10. CallMeColt

    MEP 803A Overload Fault Troubleshooting

    Everyone, I know there are a few threads on this already. Have read through them & learned from them. Used that & have troubleshooted, but am still a but stumped. My situation is a little different, so I will try to consolidate what I have done as much as possible so that I can get some...
Top
AdBlock Detected

We get it, advertisements are annoying!

Sure, ad-blocking software does a great job at blocking ads, but it also blocks useful features of our website like our supporting vendors. Their ads help keep Steel Soldiers going. Please consider disabling your ad blockers for the site. Thanks!

I've Disabled AdBlock
No Thanks