  1. PeterD

    MEP-004A parts, and problems

    What is the throttle control (that knob below and right of the instrument panel) set at?
  2. PeterD

    MEP-004A parts, and problems

    (the famous were this my problem answer... :-)) 1. I'd consider trying the following: The injection pump is gravity fed, I'd rig up a temporary fuel tank and see if it keeps running. I'm going to say that I think it will stall. I know you checked the check-ball but did you check all the fuel...
  3. PeterD

    MEP-004A parts, and problems

    What is the oil pressure gauge reading? You must hold the start/run switch in the start position until you both have oil pressure, and the unit is generating power (the volt and frequency meters register approximately the correct values, they may be off by a bit.) It sounds like you don't have...
  4. PeterD

    MEP 003a back together...but...

    CRx signifies a diode, not a resistor. A resistor would be Rx, and a capacitor Cx. Transformers Tx, while vacuum tubes Vx.
  5. PeterD

    Commercial Transfer Switch questions

    Yea, for some reason they did clip those to prevent a breaker installation there. I have no idea why, but clearly they intended that space not be used for a breaker.
  6. PeterD

    Repairing a ASK kit

    I would think that rubber insulation might present a fire hazard, while the fiber board is basically fire proof. I think you can get the fiber board from most any HVAC shop that builds ducts, or perhaps a place that sells HVAC supplies or even maybe Grainger? :-D
  7. PeterD

    Connecting MEP to house

    It is not as simple as that... Issues include bonded neutral and if the generator is permanently connected or is not permanently connected. Regardless, it is not an error to ground with a grounding rod, the error is to not ground and then something happens and the generator chassis becomes...
  8. PeterD

    Commercial Transfer Switch questions

    No, that 'open' slot next to the main breaker is not going to work. No connect for the breaker on the buss bars!
  9. PeterD

    mep-003a skip and puff smoke

    Possibly either low compression in one cylinder or an injector/injection pump problem? Color of smoke (white/gray/black?) A video might help diagnose this, can you shoot one?
  10. PeterD

    Commercial Transfer Switch questions

    My 2cents I have two of these transfer switch boxes for my setup. 1. I would be leery of running a 25 amp load on those breakers. They are marginal at best, I've seen them fail when abused. 2. No, you cannot bridge, but you could buy another one and run two boxes. I did that in my...
  11. PeterD

    MEP-005 fuel level sending unit

    Not surprising, since I'm referring to your problem with the frequency meter! rofl
  12. PeterD

    MEP-005 fuel level sending unit

    Just a thought... Pull of the sending unit and see if there are some adjusting potentiometers on the back (may be two.) Note their setting, and with a screwdriver swing each adjustment from minimum to maximum a few times, and stop where they were previously set. That may resolve the problem...
  13. PeterD

    MEP-004A recovery, smooooooth....

    You will need to run for a while, with a load, to get the temperature up much. The engine and cooling system is a bit too efficient, IMHO! It is possible, however, you have a stuck open thermostat. It is located at the upper radiator hose attachment on the engine. Run the set for about 20...
  14. PeterD

    MEP-004A recovery, smooooooth....

    1. Adjust the volts knob to read about 208. That should be confirmed with a known accurate voltmeter as well. 2. The frequency knob on a MEP-004 does nothing. It is not connected. You adjust frequency with the throttle knob (below and right of the instrument panel). My initial setting is for...
  15. PeterD

    MEP-004A recovery, smooooooth....

    Sorry, brain fart on that one. I'm not sure what I was looking at when I made that comment! Don't worry about the ether start can--I've never used mine and suspect I won't need it. (At least I hope so!)
  16. PeterD

    MEP-004A recovery, smooooooth....

    I'll see if I have one, but I don't think so. Fuel selector valve... Humm, something doesn't look quite right there. The hose clamp is for the ether start bottle which is missing--these are common and can be bought at better parts houses, or online.
  17. PeterD

    HZ question...

    Canada uses 60 HZ the same as the United Sates. All of North and Central America is 60 HZ, though voltages do vary somewhat when going south. The US and Canadian power grids are interconnected.
  18. PeterD

    bad mep002a rotor

    Yes, what coils did you measure? The ones in the rotor (input), or the stator (output)? As Speddmon mentions, they are difficult to measure the resistance of. Only easy test is for shorts to ground (all windings are isolated with respect to ground, but you still have to follow the exact...
  19. PeterD

    MEP-002A Woes

    When doing tests such as diode checks, you must use the exact meter specified. Some meters reverse the lead polarity in the ohms (ohms have no polarity, but diodes do, and meters do...) So it is possible that the reading is opposite from what the manual says it should be. For a diode test, low...
  20. PeterD

    MEP-005A Running Smokey

    If your research project is to compare different fuels, then you must do that comparison--not rely on design or specified fuel consumption numbers. If one of my students came to me and presented a comparison based on book values to alternative fuel values, I'd make him do it properly.