I was looking for a way to load test my MEP802A and had an idea:
I happened to have an old heat pump air handler laying around. The air handler has a 15KW heating coil pack installed for aux heat. Now, 15KW is too much for the 802A, however the coil pack consists of 3 separate 5KW coils...
I have been working on a 2002 MEP802A purchased from the GovPlanet auction. Original symptom was no generator output with the engine running. I dug into the exciter circuit, and found the crankshaft sensor was backed out of adjustment. After adjusting to spec, the generator "excites" and...
I found this site while troubleshooting my MEP-802A. I have a knack for taking on unusual "projects" and this generator is no exception!