Hope you had a fine Thanksgiving sir...
No the knuckleheads on site wouldn't even know about the NATO slave cable/receptacle...and from what I gather, they added a battery into the 2 x 12 VDC batteries in series mix, by paralleling the third to one of the two in series...yeah
I obviously...
Yes sir...A little background...I work for a company which is also a DoD Contractor and while I'm in Michigan, these US Army owned Generators are in Japan, so getting to the cause of problems has been difficult...None of the original crew remains on site, so background is less than reliable, but...
I have been tasked with troubleshooting a pair of MEP805-A Generators, which are both running fine (and at correct frequencies), but will only make very low AC Voltage...The average L-L VAC between the two is about 18, and the average L-N VAC is about 30...and these readings are consistent...