  1. 155mm

    Actual Rating for MEP-804B

    Bontonjeff, did you get the answers that you were looking for?
  2. 155mm

    Actual Rating for MEP-804B

    Ok so single ph is 2 legs of 120v, 240v measured leg to leg. 3 ph is 3 legs of 120v, 208v measured leg to leg you can use a 3 ph generator to get single ph by using only 2 legs. But you will only have 208 v 804 805 806 are 10 wire generators therefore they cannot be reconfigured to a true...
  3. 155mm

    Actual Rating for MEP-804B

    10kw constant with 10% surge if you use 2 legs of a 3ph generator. 2/3 of rated capacity. the tm states you can use as single ph, use terminal 1 and 3.
  4. 155mm

    Actual Rating for MEP-804B

    The voltage reconnection board is only used for selecting required voltage...120/208 or 240/416
  5. 155mm

    Actual Rating for MEP-804B

    You can get 2 legs of 120v, but across both legs is only 208, not 240v. Generator will produce about 5 kw per leg, so single phasing a 3ph genny will only get 2/3 rated power
  6. 155mm

    Actual Rating for MEP-804B

    Jeff, you do understand that an 804 is a 10 wire not 12, correct?
  7. 155mm

    Actual Rating for MEP-804B

    Yanmar turbo motor is only thing i know of, someone else will pipe up and correct me
  8. 155mm

    Actual Rating for MEP-804B

    804 is a 10 wire head, not 12. I load tested my 804a at 18k with no issues, it didn't like 21k. The video is after a used motor swap, so it was smoking more than normal to blow out the cobwebs https://youtu.be/HZuCSmFHLV4