    MEP002a panel lights out

    See reply #5, the only breaker on the entire DC side is on the front panel and kills EVERYTHING. So if your panel lights work, the breaker has not popped. Check for 24V at the cannon plug for the pumps. Do you hear any of the pumps in either aux. fuel or prime/run position? You have 3 pumps in...
  2. R

    MEP002a panel lights out

    If you have 24V from the switch, then look for 24V at the bulb sockets. Also check for ground at your bulb holders. If you have power to the sockets and the bulbs are good there is only one other possibility.... no ground. The only fuse ( circuit breaker ) on the DC control side has to be good...