    "Universal" Wiring for MEP002 and 003

    I would like to see some real world examples of the voltage going so high that the windings are damaged. It takes a lot to cause this to happen- any appliances would fry before the voltage gets so high the insulation is damaged. I believe on these generators the insulation is rated for 600V. If...
  2. K

    "Universal" Wiring for MEP002 and 003

    Are you going to be running this in a 24/7 full time operation? If so, then you want to balance the loads as "best possible". As long as you are not overloading a particular phase, I don't see any problems with temporary operation like this. I have seen many 3-phase generators running a load on...