Ok so single ph is 2 legs of 120v, 240v measured leg to leg.
3 ph is 3 legs of 120v, 208v measured leg to leg
you can use a 3 ph generator to get single ph by using only 2 legs. But you will only have 208 v
804 805 806 are 10 wire generators therefore they cannot be reconfigured to a true...
10kw constant with 10% surge if you use 2 legs of a 3ph generator. 2/3 of rated capacity.
the tm states you can use as single ph, use terminal 1 and 3.
You can get 2 legs of 120v, but across both legs is only 208, not 240v. Generator will produce about 5 kw per leg, so single phasing a 3ph genny will only get 2/3 rated power
804 is a 10 wire head, not 12.
I load tested my 804a at 18k with no issues, it didn't like 21k.
The video is after a used motor swap, so it was smoking more than normal to blow out the cobwebs