  1. AN/ARC186

    Electrical Outlet Box

    Trace taping is not permitted for this gauge wire, it has to have the properly colored jacket, The minimum wire gauge for portable cords for a 50 amp supply is 6 gauge. the thhn in your box appears to be 12 gauge and you stated the connecting cord is 10 gauge. the cord needs to be changed out...
  2. AN/ARC186

    Electrical Outlet Box

    Actually, since the box is being used for a distribution application it does fall under the NEC. Internal wiring on gensets does not fall under the NEC however portable cabling and devices connected to them does. (things like cords, adapters, etc) 34 years as an Electrician as well as 10...
  3. AN/ARC186

    Electrical Outlet Box

    Looks good, but I see a problem or two. From NFPA 70 200.6 Means of Identifying Grounded Conductors. A Sizes 6 AWG or Smaller. An insulated grounded conductor of 6 AWG or smaller shall be identified by one of the following means: (1)A continuous white outer finish. (2)A continuous gray...