    2011 Mep 803 wiring for house

    Howdy, KISS Don't over think it. In the field, ground rod in the ground, wired to generator, bonding strap in place. At a house with a Service Panel, 4 wire connection with bonding strap removed. :hammer:
  2. Daybreak

    2011 Mep 803 wiring for house

    Howdy, Connected to a house, bonding strap disconnected. In the middle of a field, bonding strap connected, and ground rod in the ground.
  3. Daybreak

    2011 Mep 803 wiring for house

    Howdy, 4 wires need to be connected to your house panel. Bonding strap is to be disconnected on generator. Wire of size, and circuit breaker of size.
  4. Daybreak

    2011 Mep 803 wiring for house

    Howdy, Yes, Type W cord is known as mining cable, and portable power cable.
  5. Daybreak

    2011 Mep 803 wiring for house

    Howdy, 6 AWG Type THHN or THWN-2 has a amperage rating 75 6/4 AWG SOOW cord has a amperage rating 45 6/4 AWG Type W cord has a amperage rating 87
  6. Daybreak

    2011 Mep 803 wiring for house

    Howdy, MEP-803A 10 KW connection to house. Your wire size looks a little small. use proper rated wire. 6/4, with all 4 wires connected. ( 2 hots, 1 neutral, 1 ground) Actually if you are permanently installing it, you would be better off running conduit and using 6awg THHN wire. 6/4 SOOW is...