I've found black plastic drums an excellent fuel storage solution. I prefer to buy ones used to transport cooking oils. They are easy to clean and any trace residual oil is no issue for the fuel system of the generator.
In this situation you can't because the batteries are already in series. The best way to keep the batteries balanced is to buy a 24v-12v power supply for any 12v loads you need to drive.
Look up DC-DC buck converter. You'll find a number of options.
Go through and check all the connections behind the panel. Look for anything that is loose. Look to see if you cracked any of the diodes on the board on the left hand side. Think about anything that could be affected by the generator being bumped around.
I saw that on the webpage. Make sure it is printed on the wire itself before you buy it. Its not a bad idea to snap a photo of the label on the side of the reel. It will have all the ratings on it. Saves trouble later.
Hahaha, yea. In this case you are getting a bargain. I'm an EE who is also a licensed electrician. Well, my licence hasn't been active in a long time but I have to keep up with the code since I do design work. I don't work in the field anymore.
I have to add, you need to check with the local...
Using individual conductors in a conduit is my preferred method where practical. You can't run individual conductors outside of a conduit or box. You would need to run conduit all the way to your termination box or set a junction box and transition from individual conductors to a cable that...
Nope. You MAY be able to get away with that cable if its in conduit above ground (depending on the temperament of the inspector).
If you put the conduit below grade it is considered a wet location. You will need to use cable rated for wet locations. Sorry. :(
FYI - That cable isn't rated to run between the generator and the structure. It is for indoor use only. You need a different kind of cable to run out to the generator.
Obviously it will function but it would fail an inspection.
#4 or #6 would be appropriate for 60a depending on length. You are good on amps. Voltage drop ends up being the limitation as the leads get longer. #6 is good up to about 100' and #4 for over 100' and up to about 250'.