  1. DieselAddict

    Finally joined the MEP-803A club...

    I know I've written up the grounding thing several times. Totally agree it needs to be a sticky.
  2. DieselAddict

    Finally joined the MEP-803A club...

    That should do it. :)
  3. DieselAddict

    Finally joined the MEP-803A club...

    5400w @ 240v is ~23 amps. That will require a 10 gauge wire between the generator and heater. The dryer elements will need a decent airflow across them to prevent them from overheating and burning in two. You won't be able to stick them in the oven and use them in that way. You'll need to build...
  4. DieselAddict

    Finally joined the MEP-803A club...

    You'll need to check the wire sizes to make sure you won't overload anything. If its a self cleaning oven its likely that it runs both elements already when running the cleaning cycle. Many also run both elements when preheating.
  5. DieselAddict

    Finally joined the MEP-803A club...

    Exactly.