  1. Guyfang

    Part Source for newly adopted 803A?

    Open to see answers/Questions.
  2. Guyfang

    Part Source for newly adopted 803A?

    Testing the relay. When not energized: Pins 7 & 4, 8 & 5 and 9 & 6 should be open. Pins 7 & 1, 8 & 2 and 9 & 3 should be closed. When the relay is energized: Pins 7 & 4, 8 & 5 and 9 & 6 should be closed. Pins 7 & 1, 8 & 2 and 9 & 3 should be open The relays are marked next to the socket. Time...
  3. Guyfang

    Part Source for newly adopted 803A?

    No, I was referring to the gauges reading output voltage. And no, I was not aware that you are not supposed to turn the AC Voltage Reconnection Switch while running. Both the -10 and the labels say make sure you disconnect load before switching, I did not see it say not to switch it while...
  4. Guyfang

    Part Source for newly adopted 803A?

    The 120 volt outlet is always powered up, as long as the GFI is working and turned on. Is that where you got your 120/240 volt reading? Or just looked at the meter? So, GENERATOR SET FAILS TO GENERATE POWER, would be your first troubleshooting step. And you do know to not turn the volt...