    MEP-016b/MEP-701a A/C Hookup Confusion

    Yeehaa, where are you finding the surge rating of 200% for 10 seconds, the only place I find that reference is in the test schedule in -34 manual where it seems to be referring to the max short circuit trip time for the breaker which you have noted as a minimum of 54 amps (maximum of 70). Ike
  2. I

    MEP-016b/MEP-701a A/C Hookup Confusion

    I would opt for the other way around, if it is for both the MEP-701 has a much larger reserve starting capacity for motors than a similar sized civilian unit (I think it is 400% of rated load for 30 seconds). Ike p.s. note when you have a generator wired for 120/240 you will be drawing from...
  3. I

    MEP-016b/MEP-701a A/C Hookup Confusion

    It took a moment to figure out your question, those knobs are to control what the voltage meter and the amp meter are reading (many of the positions are only useful when set for 3 phase), it helps to understand how a generator works to know what your looking at. I know you have a storm on the...
  4. I

    MEP-016b/MEP-701a A/C Hookup Confusion

    A couple of notes, first note the mistake in the 240V connection diagram you posted from the tech manual (marked 120V). Also be aware at least in my case the front panel convenience outlet is wired up as a single 15 amp outlet with 2 spare fuse holders. So it is probably best not to trust...