Proper connection of an external frequency meter is essential for proper reading. A loose connection can cause false readings. There is not much current as the meters are very high impedance.
Only the 10 kW came in a 400 Hz version which have a 20 pole field.
If you are loading the generator with a motor, especially a universal motor (drill, saw etc), the low power factor can cause a digital frequency meter to go batty.
Since you are new here, be very careful with using the...
Running an 002/003A at frequency lower than 55 Hz can overload the output transistor on the voltage regulator.
Frequency is set by engine RPM. It is impossible to get 400 Hz from a 002A unless you were to replace the field with a 20 pole unit and run it at 2400 RPM. It has a 4 pole field...