  1. K

    mep 003a new owner

    Just tighten until snug enough that you would never be able to pull the wire out. I don't think you can get a torque wrench in there to actually see st a specific value. Normally it comes with a special wrench to tighten the split bolts. I use what ever I have available.
  2. K

    mep 003a new owner

    According to the connection chart in the TM, if you connect a load between L1 an L0 you will get 0 amps. The 120V connection is to be made between L3 and L1 (or L0). You should be able to get 104 amps on each line. So I would say that the breaker on L3 would have to be rated ~104A, L1 ~104A...
  3. K

    mep 003a new owner

    Did you look at the dataplate? 120 only is 104 amps. If you are connecting to your house you need the 120/240 witch is 52 amps per line, you get two hot wires in this config. 120 only config gives only one hot wire.
  4. K

    mep 003a new owner

    I would just look at the data plate. It clearly states 52 amps at 240v. When I size wire for a generator I always use nameplate data. Keep it simple.
  5. K

    mep 003a new owner

    Computers don't care much at all about frequency- I would bet your computer will run just fine on 50HZ if that is what you had. The power supplies just rectify the AC to DC, no frequency at all.