Steel Soldiers now has a few new forums, read more about it at: New Munitions Forums!
Microsoft MSN, Live, Hotmail, Outlook email users may not be receiving emails. We are working to resolve this issue. Please add support@steelsoldiers.com to your trusted contacts.
Just tighten until snug enough that you would never be able to pull the wire out. I don't think you can get a torque wrench in there to actually see st a specific value. Normally it comes with a special wrench to tighten the split bolts. I use what ever I have available.
According to the connection chart in the TM, if you connect a load between L1 an L0 you will get 0 amps. The 120V connection is to be made between L3 and L1 (or L0). You should be able to get 104 amps on each line. So I would say that the breaker on L3 would have to be rated ~104A, L1 ~104A...
Did you look at the dataplate? 120 only is 104 amps. If you are connecting to your house you need the 120/240 witch is 52 amps per line, you get two hot wires in this config. 120 only config gives only one hot wire.
Computers don't care much at all about frequency- I would bet your computer will run just fine on 50HZ if that is what you had. The power supplies just rectify the AC to DC, no frequency at all.
Sure, ad-blocking software does a great job at blocking ads, but it also blocks useful features of our website like our supporting vendors. Their ads help keep Steel Soldiers going. Please consider disabling your ad blockers for the site. Thanks!