  1. Light in the Dark

    mep802a max voltage setting

    Yes push the button in, then pull the cable out, and release the middle button. This should lock into place. All this is doing is adjusting the gross RPMs up. The turning motion of this cable is what does the fine adjustment to tune the RPMS to match up to your desired hertz reading. If you...
  2. Light in the Dark

    mep802a max voltage setting

    You need to pull that throttle cable out, and reset the hertz as needed. Dont run the machine at sub 1800, its not good for the electronics. You might find the voltage range changes if you are running at proper RPM. Not doing so can damage the VR.
  3. Light in the Dark

    mep802a max voltage setting

    How do you have the machine set, not only at the S8 but also on the faceplate gauges? What hertz are you running at, that you are determining this? Do you have the throttle pulled all the way out, and adjusted correctly?