nothing...same thing... I don't know why I just bothered to find out how much the output of the 10K generator is. But according to the Data plate the output is 32amps at 208V 3 ph . So that's is a bit off from the number of 60amps, which it said the FDECU requires in the TM
P.S. the MEP 804 puts...
I am running the generator as we speak for 2 hours with the fan on. I'll see if then I turn all off but the compressor, that it will come on in maintenance mode.
Still would like to know what kind of generator is supposed to run these. And if there is someone here who actually worked on these units
I may have found what could be my AC start up problem
note the bit where it mentions a 16K 60 amp power source. Now that is for a FDECU 2 but I could imagine it's not too far off for my FDECU 5 since my 10k generator gets hopelessly overloaded
Yes, I believe so
I also went by the diagram on top of the unit which indicates the same?
when I get home I'll fire up the unit and make note of the way the fan turns. If it's hooked up wrong it out to turn the opposite
I also checked all three posts on the generator, they all produce the same current.
To double check
L1 - red
L2 - black
L3 - orange
white - neutral (Lo)
Green - ground
grounded the genset too
Correct , sir
phasing is hooked up right . I found a problem was with the generator. a clip on wire on L2 cane off.
with that fixed the unit will power up and blow air , as the fan is working. Heat works fine , too.
Now when I try and turn son the ac , it will turn the fan ...and after a while...
Yes, sir there is a remote I tried both ways. It doesn't go into 'fail safe mode' so I guess it's something simple.
I have two units that both seem to do the same thing.
on one unit the bolts of the electronic unit were lose, so I assume the issue is not with my generator.