  1. P

    need advice with FDECU 5

    Pretty sure the manual says you need a 60 amp power cord...not that it will need 60 amps in general...now you may get a spike when the compressor fires but it will be momentary... Unless you have a super high-speed amp meter it will likely miss a spike but you should be able to measure the...
  2. P

    need advice with FDECU 5

    Do you have an amp clamp? Measure the amp draw?
  3. P

    need advice with FDECU 5

    Nicely done...congrats... What are you going to cool with it?
  4. P

    need advice with FDECU 5

    Yeh, your 10kW may have pooped himself a little....
  5. P

    need advice with FDECU 5

    I guess I missed the '10kW generator' post... Unless it is uber efficient or massively inefficient, a 5ton Mil ECU will typically run at or around 10kW on the gen...so to start it with the motor surges etc. you would likely need 15 to 20kW...preferably 20kW depending on the generator and its...
  6. P

    need advice with FDECU 5

    Convention is Black for L1, Red for L2 and Orange or Blue for Phase 3....hard to believe the ECU would not have a phase monitor to stop running backwards but let's hope Guy is right and it is a simple fix...