    MEP002A no output

    CVT1 has control windings. By passing DC through them, the iron in the transformer can be made to saturate so that the transformer produces less current to be rectified and sent to the exciter field. To test CVT1, the rectifier bridge, and the associated wiring, you can disconnect terminal 14...
  2. Triple Jim

    MEP002A no output

    I built one and would be happy to test yours for you, but I imagine shipping back and forth just for the test would not be worth it to you.
  3. Triple Jim

    MEP002A no output

    There is, on page 6-12 of manual TM5-6115-585-34, but it takes a couple meters, a variable transformer, and T1 and T2 from the control box.
  4. Triple Jim

    MEP002A no output

    Don't assume the regulator is bad if you haven't tested it. The problem could be something as simple as another broken wire.