    how to hook up auto starter kit to MEP 803A generator?

    TB#2 provides +24V DC. TB#3 receives the +24VDC. The generator will go through startup sequence, start up and run as long as power is applied to TB#3. When the power is removed from TB#3 the generator will go into shutdown routine. This detail is provided in the installation manual from Innova...
  2. I

    how to hook up auto starter kit to MEP 803A generator?

    TB#10 goes to K8-12 TB#9 is jumpered to TB#1 This is if you do not have K-Ext or ATS wired in. This will cause the load breaker to close after the warmup period. (This piece is missing from the documentation) I cannot speak to what terminals the ATS is wired to - I do my load transfer and...
  3. I

    how to hook up auto starter kit to MEP 803A generator?

    The K-Ext kit will disconnect service while the MEP goes through the cool down cycle as I understand it. Without it the autostart will go through the cooldown with the circuit still energized on the MEP. K-Ext is an optional component you can purchase from Inova. It does not come standard with...
  4. I

    how to hook up auto starter kit to MEP 803A generator?

    a) Download the manual from the same site. The step by step instructions are in there, including pictures. b) Same site also sells an ATS. c) Depending on how cold or how hot it gets in your valley you may also want to consider installing the K-Ext kit with the autostart kit to provide an...