    MEP-804B Governor control issue

    I took the generator in to have it looked at by a generator repair shop that had a recently retired 91D. After seeing it do its random acting up and running some test he told me, I need to replace the Woodward unit. It's part number 8270-1096. Any idea where I can find a replacement? Or even...
  2. J

    MEP-804B Governor control issue

    When the A5 takes control I have seen it do that before. To me it acts like it is starting and adjusting to its own settings. The voltage is normally very stable accept when it’s switching control. I expect the frequency to go high when I have the frequency set for using R2 (which I should not...
  3. J

    MEP-804B Governor control issue

    I have installed the new MPU from Green Mountain Generators . On the MPU I'm getting 2.813V AC and 972 ohms (test the part before install and at the A5). I still have the same issue. I did get the issues to reproduce for a short time as seen in the two videos. The first one show where the R2...
  4. J

    MEP-804B Governor control issue

    I don't have a spec for it. To eliminate this problem, I ordered the exact part from Green Mountain Generators. Once it arrives I will install it and report back.
  5. J

    MEP-804B Governor control issue

    I have the same ohm’s at the MPU as I have at 148C and 147C. Wires unhooked on both tests. What should I do next?
  6. J

    MEP-804B Governor control issue

    I was able to get one on Amazon MSP6729. I had to turn it about 1/4 a turn outward to get around 2.79v. 3/4 of a turn gets me ~0.6v. I can't get it much higher as it will be to close. I haven't seen any changes on the A5. I still have control of the R2. What should I do next? I get 303.6 ohm's...
  7. J

    MEP-804B Governor control issue

    I cleaned it, and was having trouble adjusting it, when the end of it was chopped off. Where can I buy another MPU? Will something like this work from Amazon? https://a.co/d/f7kP6zA
  8. J

    MEP-804B Governor control issue

    I get ~5.514 v DC on 9 and 10 of the A5 . On 16 and 17 ~5.120 v AC.
  9. J

    MEP-804B Governor control issue

    I didn’t receive any sheets. Also do you have a link to documents, this way I can reply properly.
  10. J

    MEP-804B Governor control issue

    Randomly, the computer will control the frequency, prompting me to make fine-tuning adjustments using a small screw on the Woodward. When the computer does not take control, I have to readjust the screw, allowing me to manually set it to 60Hz using the front knob. Video link of me using the...
  11. J

    MEP-804B Governor control issue

    I have a MEP-804B generator with the control for the frequency will randomly switch between the governor computer and manual control knob. I can adjust the fine tuning, but it’s different tunings for both. Seems like it’s worse when the weather is in the extremes. What do I need to do to...