    MEP 831a No Power To Main Bus

    Glad to help you out!
  2. K

    MEP 831a No Power To Main Bus

    For now install the jumper knowing the risk. Use the electric start and close the contactor so you can charge your battery bank for now. We can address another way to do the test later.
  3. K

    MEP 831a No Power To Main Bus

    When you have time and you've charged you batteries please do the following test. Leaving S1 in the STOP position lift the actuator off the magnet. Press the compression relief lever. Pull start the set. Measure the AC voltage across the A & B terminals on the Governor Controller. Shut the...
  4. K

    MEP 831a No Power To Main Bus

    In a pinch you can bypass all the safety systems by installing a jumper wire between S5-5 and chassis ground. This will allow you to close the contactor by using S5. **** Doing so will prevent the set from opening the contactor due to any fault **** Proceed at your own risk
  5. K

    MEP 831a No Power To Main Bus

    Since the speed is cycling up and down and the set isn't shutting off correctly the next thing to check is the spring on the mechanical governor. Below is a picture showing which hole in the arm that the heavy green spring needs to be hooked thru at each end. The picture is with the mechanical...
  6. K

    MEP 831a No Power To Main Bus

    If the engine RPM is too high and it doesn't shut off properly it leads me to suspect the linkage on the mechanical governor isn't adjusted properly. At no load the gap between the magnet and the "target" on the governor arm should be ~5/16". If the gap is too wide it can cause problems with...
  7. K

    MEP 831a No Power To Main Bus

    Those reading make much more sense :) Your readings are indicating either an issue inside the inverter (K8 inside the inverter is not closing) or wiring external to the inverter has an issue. Another possibility is that the engine is running at too low an RPM. With the set running measure the...
  8. K

    MEP 831a No Power To Main Bus

    As I mentioned earlier something isn't right with the DC voltage readings you reported. The very first one is K12-12. That terminal is suppose to be tied to ground so the voltage there should always be 0 volts DC. So Lets start over... Open the control cubes and lower it. Connect your meters...
  9. K

    MEP 831a No Power To Main Bus

    Something is amiss with your readings. I'd expect either ~0 VDC or ~24 VDC at each reading point. Readings around 12-13 volts are not right. Readings need to be done with S5 held in the UP position. The first one that's not right is K12-12. That terminal on K12 is tied to ground and the...
  10. K

    MEP 831a No Power To Main Bus

    First thing to look at is the far left relay inside the panel. This is K12 the fault relay. If the tiny LED inside it is lit then there is a fault and the contactor will not close. Is K12's LED on when the set is running? If K12's LED is off... Here are a sequence of test steps to narrow down...
  11. K

    MEP 831a No Power To Main Bus

    Do you have a hand held meter and are you proficient at using it?