    Valence's M116A3 Mounted MEP-803A (10kw generator)

    I suspect the red fuse was an amperage rating less than 3 amps or possibly not a time delay fuse which cause it to pop. The popping of the red fuse shouldn't have damaged anything. The fuse there is to protect the Quad Winding in the gen head from getting damaged should the AC Voltage...
  2. K

    Valence's M116A3 Mounted MEP-803A (10kw generator)

    What was the current rating of the red fuse?
  3. K

    Valence's M116A3 Mounted MEP-803A (10kw generator)

    Generally the Calibration steps suggest using an accurate external instrument, if available, for reference. For instance use a DMM to measure the battery voltage at the slave port while calibrating Battery Voltage. If one doesn't have external references they can go by the sets gauges if they...
  4. K

    Valence's M116A3 Mounted MEP-803A (10kw generator)

    The %Load function on my system is measuring the voltage/current that each winding pair is contributing to the load. It's actually measuring the voltage at the 3 different phase load inputs to K8 the overload relay from the burden resistors. When in 120 or 120/240 mode the %Load readings from...