    10kw gen. no power to control panel

    Where do those red and blue wires go to after they leave the top of the picture? Those are not in a normal 803.
  2. K

    10kw gen. no power to control panel

    For starters I'd suggest using your meter and see if there is 24 volts DC present on each of the terminals of the Emergency off switch. If present then check each of the terminals on CB1. If present then check S1 terminals 2,4,6 & 8. If present then put S1 in the Prime/Run position and again...
  3. K

    10kw gen. no power to control panel

    Did you check to be sure the red Emergency Off button is pulled out?