  1. K

    First MEP 803A, fix up help

    Also the L3-L1 L3 position on the AM-VM switch will cause the %Load meter to register the TOTAL load on the generator, not just what's connected to the L3 lug. It registers the load on L1 & L3 combined.
  2. K

    First MEP 803A, fix up help

    The overload was/is probably dirty contacts inside S8. When in 120/240 setting S8 connects R12 & R13 in parallel for an effective resistance of 3.75 ohms. The combination of R12 & R13 form the burden resistor across CT3. If S8's contacts for R13 paralleling aren't making contact the effective...
  3. K

    First MEP 803A, fix up help

    The reason the readings are off is because the CT's and K8 are connected in parallel to the resistors in the circuit.
  4. K

    First MEP 803A, fix up help

    A replacement for #48 is a FSOT2011E7R500JE A replacement for #49 is a FSOT2011E20R00JE A replacement for #50 is a FSOT1011E1K300JE
  5. K

    First MEP 803A, fix up help

    To check R10, 11 & 12 you need to disconnect 1 of the wires from each resistor so that 1 terminal on each has no wires on it. I think you'll find they are OK. The original resistors are no longer made. The manufacturer does make a newer version that will mount up just the the originals. I'll...