I tested the k8 and got all 3 to fault on short. On overload i got 27, 30, and 75 seconds. Manual says it should be about 60 seconds. I'm not sure what to think about that. seems to me 2 of them should trip too early and the other would take to long. I'm thinking about how this should work...
OK today I ran at 45 amps for 4 hours. I had seafoam in the tank. It had a little smoke for the first hour then it cleared up. After the 4 hours I took it up to 125% for 10 minutes. It did not trip. I then went to 133% it did not trip. I pushed it a little more and the rpm went south. Tomorrow...
On the gfci right below the fault lights. Is this a gfci for the load. If i push the test button on the gfci should it drop the contactor? I thought i read it was only for the convenience outlet.
The good reasoning to test the faults is this gen is new to me and i don't know if they work. I don't know the history of this set. At this point i have a problem with this set and i don't think its wrong to want to fix it. If it were up to me i would want it to trip at 12k but i'm not sure i...
I will start over. The way i think a generator should work is it should fault before the engine bogs down. I'm not talking a few hz, i mean really drop in hz to someting like 35. Also not just a dip. It drops and stays dropped until i disconnect the load. If the mep-803a does not work like...
To be clear, my generator did not trip. I'm starting to feel like you guys don't test your generators to the overload or short circuit fault. Can anyone comment on how many amps for what amount of time should cause a fault?
last night i couldn't help but try some more. I don't have my load bank yet so i was still using the house. I put some seafoam in and got it up to 59.7A on one lag and 60.4 on the other. It was blowing some carbon out but not a lot. About 117% on the meter. After about 20 minutes something in...
I have no plans to run this at max all the time. My problem is if my wife turns too many burners on at the same time the water heater is calling for heat our generator better fault before the engine drops and gives my house 35hz. The generator faults to protect it and right now i'm only trying...
At this point i can hold 52A no problem. Before i fixed the fuel cut off solenoid it was a problem. So i should be able to pull 62 amps without the engine dropping? How long should it do 62 amps before a trip? I will add seafoam to my tank on my test this weekend. I just ordered some dryer...
I have read about wet stacking. The trouble lights are working. I'm running new fuel. i had drained the water separator. I replaced the fuel strainer at the pump. I will replace the inline fuel filter and run the load test at 45 amps for 5 hours and report back. I understand the unit is...