    MEP-803a overload circuit

    Good to know. Ill keep it to a minimum then. I always did it to check the condition of the govenor. I do have a nordic air 36000btu of cooling /31000 btu of heating unit now. How do i step on the heating coil. About 9kw of load?
  2. N

    MEP-803a overload circuit

    Still waiting on Deoxit What the F
  3. N

    MEP-803a overload circuit

    Every unit I get I pull the top cover off and look for apprentice marks. Loose wires, corrosion, sabotage and over all condition. Then i load them to 80% @1.0ph resistive heaters for 4 hours, 100% for 1 hour Same 1.0ph then use my variac to see how much she'll suffer till she drops RPM's. If...
  4. N

    MEP-803a overload circuit

    That's what I think too is it just came back from service and was tagged cecom to have that S8 repaired. I'm not doubting the reset is meant to make these things like new. I'm just saying every time i see a unit at auction with a bunch of screws missing from the covers as if someone gave up...
  5. N

    MEP-803a overload circuit

    As you said earlier many units reused old parts from other units being reset just to get them out the door so the parts that "SHOULD" have gotten changed is where my concern comes from.
  6. N

    MEP-803a overload circuit

    Glitch in the matrix how the **** did i post that twice
  7. N

    MEP-803a overload circuit

    This unit is a 2003 and theres only 2000 hours on ithe meter so im thinking s8 is why it was taged cecom, for repair of that OL fault light. I found s8 on ebay for like $140 so worse case scenario i fubar it ill buy a new one. What exactly is "reset" ive been avoiding tier 2 units like the...
  8. N

    MEP-803a overload circuit

    This unit is a 2003 and theres only 2000 hours on ithe meter so im thinking s8 is why it was taged cecom, for repair of that OL fault light. I found s8 on ebay for like $140 so worse case scenario i fubar it ill buy a new one. What exactly is "reset" ive been avoiding tier 2 units like the...
  9. N

    MEP-803a overload circuit

    Might take a few days for the deoxit to show up via online order
  10. N

    MEP-803a overload circuit

    Im using a fluke mm to measure the voltage differential. The volt gauge showd the phenomenon too. Also all three of my units do it. Yes ill be using 2000 grit wet sand paper or even emery cloth. Problem with cycling is its not sweeping the contacts accros each other just opening and closing...
  11. N

    MEP-803a overload circuit

    Update UPDATE Since im inpatient i couldn't wait for the deoxit to come in the mail. Since i have 2 other running units sitting next to it i swapped S8 from another unit. And it worked! Now that its out you can see the contacts are completely visable from the sides of the switch should have...
  12. N

    MEP-803a overload circuit

    Which Deoxit cleaner do I get there's like 7 kinds i found online cause no one seams to carry it locally or I suck at looking locally. F5 D5 G5 D100 S5 R5 and one that has no letter number combo maybe original blend
  13. N

    MEP-803a overload circuit

    i checked all the burden resistors, diode and cap.
  14. N

    MEP-803a overload circuit

    Update Update. Looks like it only over loads when its in 120/240 but not when in 3 phase... i cycled the switches a ton that did seam to make a difference on the load gauge. Gues ill check those resistors. In 3 phase Got 100% load on L1 and L3 runs fine all day. Put 100% on L1 and L2 runs fine...
  15. N

    MEP-803a overload circuit

    Same Hey all ive got the same problem.o/l on a new mep803 i just got. I made the mep vs consumer gen video on YouTube 🤥. Ive been buying and selling these things when i can. Im well verse with electrical. I went straight to the source. I volt metered out the ct. With a 10kw kiln wire element in...