  1. sewerzuk

    New light-off of an MEP004A--engine good, not sure about electrical side

    The movable part of the voltage reconnection board should have an arrow on it. That arrow should line up with one of two voltage readings on the fixed part of the board. As triplejim stated, your set is likely configured for 240/416 right now. To change voltage, you just remove the nuts on...
  2. sewerzuk

    New light-off of an MEP004A--engine good, not sure about electrical side

    120/208 and 240/416 are the only "standard" voltages that the -004 comes configured with. So, as long as the 120/208v arrows line up on the reconnection board, the set is already running 120/208 and no changes are necessary to pull single phase 120/208. All that you would do is wire up your...
  3. sewerzuk

    New light-off of an MEP004A--engine good, not sure about electrical side

    When configured for 120/208 three phase, the generator will be producing 120v line to neutral, and 208v line to line. You can just wire up the neutral and two of the lines (any two; it doesn't matter) to your single phase house, and it will work fine (in most cases). Since your 240v loads will...
  4. sewerzuk

    New light-off of an MEP004A--engine good, not sure about electrical side

    1. Not all that uncommon to see bad meters, but I would verify it is bad by attaching a DVOM to the meter to make sure it is receiving a proper input. 2. Good! At least you're sure the set is generating power. 3/4. If you are getting voltage at the output terminals, then the breaker is...