MEP 803 10 kw Will not start from S1 on panel

Tugood

New member
4
7
3
Location
Florida
My military MOS was 52 B 20 Generator operator mechanic. That was roughly 48 years ago. Yes, I can read a schematic. Generator is new to me, and it will start and run in battle mode if I hold the magnetic plunger back in the retracted position. I was reading an old post on this non start issue and traced a 24-volt reading as far as the S1 switch. I have 24 volts up to the S1 on 2 and 4 but not on 6 and 8 terminals. Thanks for your response. I recently purchased the technical manual dated 20 October 1983 also identified as TM56115-585-24P. I am unaware of downloadable TM's. I have only started and run the genny for a short period of time as oil pressure gauge does not register and I am assuming that is part of the electrical issue. I plan on installing a direct oil pressure gauge as a secondary confirmation of pressure. Any assistance would be greatly appreciated. Jack.

 