  1. C

    MEP002A no output

    Well I load tested it yesterday and it did well, pulling all of the loads, water heater, well pump etc. and just in time, we got some drizzle this morning after a long dry spell and the dust on the distribution line poles caused allot of pole fires, we are chugging along just fine now on the...
  2. C

    MEP002A fuel hose

    For what it's worth I have been dealing with S. C. for decades and have never had a problem, maybe I have just been lucky. Craig
  3. C

    MEP002A fuel hose

    Anyone know where I can score some fuel hose for the MEP002A? I have a small leak on the hose between the sediment and first filter housing Craig
  4. C

    MEP002A no output

    We are Genen now!! reg. working fine only a couple minor issues, the freq. meter is not working and the battery charging system is not working Thanks Jim for the help! Craig
  5. C

    MEP002A no output

    Yep two shorted diodes on the A4 board and a trace burned off the back, fortunately the three windings all ohm out the same, about 3.8 ohms so I think CVT1 is OK, Jim you also confirmed my assumption on the "bucking" current. So it looks like I am on the back stretch on getting this thing to...
  6. C

    MEP002A no output

    OK after getting the regulator on the bench at work and doing some component testing I don't see any problem there, I understand how the field is exited with the start switch through CR-2 but I am having a little trouble getting my mind around what roll CVT-1 is playing in all this, ok I can see...
  7. C

    MEP002A no output

    Thanks Jim, looks simple enough. Craig
  8. C

    MEP002A no output

    Well I would not suspect another wiring issue as when the field lead (appeared to short and burn in-two) went the gen was finished, kaput, the pass transistor on the regulator tests bad, I have two of the three transistors in stock but of course not the pass transistor, hopefully I can get one...
  9. C

    MEP002A no output

    I do see above
  10. C

    MEP002A no output

    I pulled the end bell and found a broken wire, fixed that and now I am reading about 32 ohms on the field, I can hold the start switch in the "flash" position and get voltage, I assume and would not be surprised that the broken and shorted wire fried the regulator, this should not be a big...
  11. C

    MEP002A no output

    J12A and J12B, will check first thing in the morning.
  12. C

    MEP002A no output

    OK I found it, now I just need to figure it out
  13. C

    MEP002A no output

    I would like to trace out the field circuit, can anyone tell me which Cannon plug and what terminals on that plug? I am having trouble finding the schematic in the TMs Thanks
  14. C

    MEP002A no output

    Hello all from a newbe I picked up a 5kw genset this week and after re-installing the missing filters it runs fine but has no output, I found P60 and P57 (field wires) disconnected from TB3 5 and 6 indicating someone before me was trouble shooting the problem. When I ohm out the wires I get...