• Steel Soldiers now has a few new forums, read more about it at: New Munitions Forums!

  • Microsoft MSN, Live, Hotmail, Outlook email users may not be receiving emails. We are working to resolve this issue. Please add support@steelsoldiers.com to your trusted contacts.

Search results

  1. Scoobyshep

    How to size a ATS

    List of panels and what is fed from each and size of breakers Sent from my SM-G973U using Tapatalk
  2. Scoobyshep

    How to size a ATS

    Do me a favor. Get me a schedule of each panel. I might be able to help you figure out a different solution. Pics help too. Sent from my SM-G973U using Tapatalk
  3. Scoobyshep

    MEP003A Starts, but then stops either when starter released or after about 20 minutes running

    When you get it to fail jump the oil pressure switch. If it still fails jump the temp switch. See if either of them keep it running. Then you need to determine if it's a bad switch or the switch is protecting the set Sent from my SM-G973U using Tapatalk
  4. Scoobyshep

    How to size a ATS

    First of all, how big is the house to have a 400 amp service? Second the short and easy answer is it has to carry the largest current potentially applied to it. So you need a 400 amp switch. You can go smaller if and only if you setup an emergency sub panel. Put all the loads you want to run on...
  5. Scoobyshep

    Output issues with MEP701A - Power outage issue.

    Yes this. If you have a voltage adjust and you are on the low side you may be seeing excessive drop. you can safely run at 125/250 volt (doesnt seem like much but it might be just enough to kick the motor over)
  6. Scoobyshep

    Output issues with MEP701A - Power outage issue.

    You are using 8AWG for a 3000 watt generator? way overkill but shouldnt be an issue. out of curiosity what do you have the voltage set at? or is it non adjustable.
  7. Scoobyshep

    Output issues with MEP701A - Power outage issue.

    nice thought, but they usually increase wire size if its that deepdown. not to mention it would have to be fairly deep to have enough drop to impact current draw significantly
  8. Scoobyshep

    Output issues with MEP701A - Power outage issue.

    Its 3000 watt at 240 volt (approx 12 amps). And yes its quite common to have a motor draw 300% FLA on startup. In the NEC there is an entire section for motor protection because of this. Sent from my SM-G973U using Tapatalk
  9. Scoobyshep

    Output issues with MEP701A - Power outage issue.

    Well if you're up for trying it, you could install a soft start on the pump Sent from my SM-G973U using Tapatalk
  10. Scoobyshep

    Output issues with MEP701A - Power outage issue.

    Some motors dont have them. Sent from my SM-G973U using Tapatalk
  11. Scoobyshep

    Output issues with MEP701A - Power outage issue.

    Check the start capacitor on the pump and see if its in tolerance. You may be able to replace it with a "hard start cap". The unfortunate truth may be the generator may be too small. Sent from my SM-G973U using Tapatalk
  12. Scoobyshep

    Output issues with MEP701A - Power outage issue.

    Sounds like it doesnt like the inrush of the pump. Is this a new problem or have you never run this pump on this generator before? Sent from my SM-G973U using Tapatalk
  13. Scoobyshep

    Base Skid for a MEP-802

    Look for the 400hz skids too. Those are more likely to have been parted out. Sent from my SM-G973U using Tapatalk
  14. Scoobyshep

    MEP003A Starts, but then stops either when starter released or after about 20 minutes running

    Temp switch is next (need to know of its faulty or actually overheating) or fuel pump or filter clogging Sent from my SM-G973U using Tapatalk
  15. Scoobyshep

    MEP003A Starts, but then stops either when starter released or after about 20 minutes running

    Check your oil pressure switch as well. The start switch bypasses it Sent from my SM-G973U using Tapatalk
  16. Scoobyshep

    MEP-004a injection pump problems

    well atleast you were successful.
  17. Scoobyshep

    MEP-004a injection pump problems

    whenever I get into a situation of things that should move that dont my first thing to use is knocker loose, its made by crc smells like pine sol and makes pb blaster look like water.
  18. Scoobyshep

    3-wire connection bonded?

    In my years, ive done grounding from houses up to industrial and a few cell towers too. Lot of cad welding and the weirdest overkill bonding. Worst one i had to do was a 110 foot rod. That one was in a delta field so 3 rods 110 feet apart 110 feet down. When I redid my home service the inspector...
  19. Scoobyshep

    MEP-004a injection pump problems

    Yes, It looks like a bunch of stacked up plates Sent from my SM-G973U using Tapatalk
  20. Scoobyshep

    MEP-004a injection pump problems

    Little guy is a water seperator. He can be cleaned Sent from my SM-G973U using Tapatalk