It has been some time since my last post. I have updates, tips, and lessons learned.
First, Success! The MEP-802a is running well and the house is wired up for it.
Status where I left off:
1) Batteries:
a. - The work around worked! I visited a local savage yard. They...
Mike KK4AiF - Thanks for the suggestion.
I was not able to find a new battery locally for less than $110. A web search shows a $79 battery at two Home DePot stores. I called one. They said they don't even stock the size or can get one in.
------- workaround? --------
Thinking outside the...
Thanks for the next step. Will work it when I have more time.
Update:
I bought on Craigslist a used motorcycle trailer. It was a great price and was rated at 3,200 pounds. I plan to mount the generator later this weekend.
My next expense are the batteries. The trailer's tag and title...
All
The generator is working! Thanks for the help everyone.
What I think happened:
I believe the fuel in the injector pumps dried out after 20+ years sitting. A residual film was left on the pump's cylinder and piston walls. When I cranked the engine the cam internal to the motor pushed...
FYI -
Tech manual: TM 9-2815-250-24&P, Section II, figure 12, identifies the pump gasket part number. There are 3 different part numbers. They differ by thickness. The crankcase is stamped with a number that states which gasket thickness to get.
Guyang,
Thanks for the information. It was right on!
I did a test and some research. As suggested I pulled one (not both) input line. Nothing came out. So, it is likely a pump problem. The tech manual (TM 9-2815-250-24&P, pages 3-50 to 3-53) instructs removing the pump, cleaning it with...
All -
I had a little time after work to attempt it again. No luck.
Synopsis:
1) Purchased the filters through Ebay. I expect them early next week. Confirmed the current 2nd stage filter was OK to use.
2) Setup the 24-volt workaround
3) Generator configuration:
S1 master...
Daybreak, Hammick, Guying: Awesome feedback and plan forward. Thank you.
All - life got in the way. I was not able to get to the generator this weekend due to other priority items. My calendar has a few days after work this week to give it another try. I should have more time next...
Thank you, but don't fully understand. What is the "S-1"? I'll do some homework on forum.
It will be a couple of weekends before I'll have time to work it. I'll keep the
post update as I make progress.
Thanks for the tip. I'll have some time to work on it in a couple of weeks. I also found in the forum the tech manuals and the information to bleed the fuel system. I'll report my findings.
Hi,
I recently acquired a 1994 MEP-802a with 20hrs. Inspection suggests it has the original 20hrs and not a refurbish unit. Need help in starting it.
My first attempted to start it I found the injector return line leaking everywhere. Over the years it looks like the line became putty-like. I...
Hi,
I recently acquired a 1994 MEP-802a with 20hrs. Inspecting it suggests it is the original 20hrs and not a refurbish. Need help in starting it.
My first attempted to start it found the injector return line leaking everywhere. Over the years it looks like the line became putty-like. I...