  1. Triple Jim

    Mep 002a Starter Issues

    It would seem that there is something mechanically wrong with the speed switch or the mechanism that's driving it.
  2. Triple Jim

    Mep 002a Starter Issues

    If you jumper just the terminals on the switch, it should tell you if it's the switch or the wiring.
  3. Triple Jim

    Mep 002a Starter Issues

    It looks like it prevents backfeeding relay K3 through R1 (on diode board) when the generator is running. I woudn't have thought that could happen though. I wonder if the starter disconnect switch has something strange going on. Try shorting out its terminals and cranking the generator...
  4. Triple Jim

    Mep 002a Starter Issues

    The starter solenoid on the motor should have a contact that makes it go from pull-in (high current) to hold (lower current) once its core pulls in. If the hold coil or connection is broken, then it would pull in, and with nothing to hold it, release, then the contact would close and it would...
  5. Triple Jim

    003a unstable voltage

    Jimmy, no need to pay since it's guaranteed for at least two years. I don't argue about what caused the failure, and I may make changes to prevent future damage from a failed CVT1 based on your experience, so it'll help both of us.
  6. Triple Jim

    003a unstable voltage

    It's T1 that supplies power through CR8 CR9 and CR10 to that resistor. If something caused the 18v zener diode CR6 to fail shorted, R11 could overheat. I suppose that if the control winding in CVT1 shorted to another winding, it could have put current into that control loop and caused the...
  7. Triple Jim

    4K military not putting out much.

    The peak is likely to be at least five times the running current, from measurements I've done.
  8. Triple Jim

    003a unstable voltage

    That's why I asked if it was cyclic or random. Cyclic points toward an unstable control loop, so reducing the feedback constant by adjusting the pot could help. Random would make me look for a loose connection or bad solder joint somewhere.
  9. Triple Jim

    003a unstable voltage

    See if turning down the sensitivity pot helps. I labeled it "transient response" on the board, and it's the pot next to the voltage adjust pot. Normally you don't need to adjust that pot from where I set them during test, but your generator may have a little too much "uniqueness". The second...
  10. Triple Jim

    003a unstable voltage

    Is the instability cyclic, or random?
  11. Triple Jim

    Question about the HZ on a MEP-803a

    I wouldn't want to be on the downhill side of a ramp with a 1,300 lb generator on a pallet jack above me. Maybe use a rope wrapped around something a couple turns to ease it down, capstain style.
  12. Triple Jim

    Bad Oil Pressure Gauge

    That's an ordinary pressure gauge, so any type you like that fits and has a reasonable scale will work fine.
  13. Triple Jim

    Bad Oil Pressure Gauge

    Any decent pressure gauge with the right fitting will work fine if you're not trying to stay 100% original.
  14. Triple Jim

    4K military not putting out much.

    Or at least the running current if you don't have "peak-hold" on your clamp-on meter, since starting current comes and goes very quickly
  15. Triple Jim

    House Voltage... Does it really matter?

    UPSs have arbitrary alarm settings like that. Some are programmable to any voltage you like. I had one that occasionally beeped when on generator power, probably as things like the well pump started. That one has a menu system and I was able to adjust the low voltage alarm lower to make it...
  16. Triple Jim

    Off road Diesel in a 2011 MEP 803

    As far as I know, offroad diesel is normal fuel with dye in it, with no other difference. Nothing I've read contradicts this, except some Internet guessing that offroad diesel is not low-sulfur. I doubt if it is any different from road diesel, because I doubt that refineries would make...
  17. Triple Jim

    House Voltage... Does it really matter?

    Back in the days of incandescent bulbs, a few percent high would shorten their life more that that few percent. In those days I probably would have talked to my power company if the voltage were consistently more than the plus 5% spec. If nothing were done about it, the alternative was to buy...
  18. Triple Jim

    House Voltage... Does it really matter?

    It doesn't matter. I'm often around 125 here. In general, 10% voltage errors are no problem for any device. That would mean a range of about 108 to 132 volts, or 216 to 264 volts. But decide for yourself, of course.
  19. Triple Jim

    4K military not putting out much.

    Please supply us with some details about this air conditioning unit, including capacity (tons) and the current rating. I've come across motors that when starting, actually draw 10 times the running current briefly, as measured with a high quality meter with a peak-hold feature. My MEP-003A...
  20. Triple Jim

    Transfer Switch Installation Costs - Your Opinion

    Of course you do all the wiring but don't connect it to the entrance panel. Then you pass inspection, then you coordinate with the power company to connect it.