Went ahead and pulled a pump and filter known to be be good and installed on the unit.
ran fairly steady for 19 min and began to droop.
drooping continued for another 10 min. Until it was swinging like a pendulum between 56 and 64 HZ
seems like it takes it longer each time to fail. It started...
Got it.
sounds like we’re testing the primary.
I have another identical unit sitting next to it that runs flawlessly.
does it make sense to swap the primaries out or switch with the auxiliary ?
am looking for a replacement for the small filter.
took it off awhile back and it looked fine and had...
had another go at it.
unplugged the A2 fault indicator or the malfunction indicator as described on the schematic.
thought we had a chance for awhile. Took 15 minuet’s to begin drooping. Temp never exceeded 180 degrees.
oil never went below 42 psi. When the drooping became excessive I shut her...
Have not adjusted the frequency.
it continues to run well for 10 to 15 minuets. Have changed the filters and drained the fuel tank and scoped it.
no dirty filters or debris. Have a clear stack and oil and temp readings look good.
it consistently begins to droop after it reaches operating temp...
Update on the Mep 803 a.
hours on the machine are 209 total. Changed filters and checked fuel cap.
it was rusted and turned off.
repaired rotten return line. Engine will now run normal for six minuets.
had electrician check output. Appears normal.
never put it under a load.
As soon as the...
Have a low hour 10 k MEP-803A generator.
located south of Dallas. In need of someone who can work on mine.
it runs and puts out, but won’t run at a steady Rpm.
thanks