sorry had to get back to the office, Amazon, Wix 33511. buy 3 of them. use 1 gasket in the strainer, use the other 2 to replace the filters and gaskets. the unused filter can be used later with the replaced but slightly used gasket
Fuel strainer or fuel filter?
When you buy the new wix fuel filters they come with a gasket that can be used to replace the top end cast or gasket however they don't just sell the gasket so if you need one for the strainer what I've done in the past is buy a fuel filter and I just reuse the...
glad it worked. do yourself a favor and buy a can of deoxit. apply a small amount to the resistor windings and sweep it again, this will clean and help protect it from oxidizing again.
Central FL and inland. Had a branch hit utility. Got about 45 min of runtime. Very glad to have the meps available
Sent from my SM-S908U using Tapatalk
Ebay is your friend. I can also look and see if i have a spare in my shop.
If you apply 24v to the pump (preferably through the circuit breaker) and you hear it run the caps are still good
The problem is there is no protection (circuit breaker)
So you can jump the pumps to power and they click? if thats the case then there is a wiring fault we need to dig into.
click the TM tab up top go to generator and electrical TMs about 4 pages in is all the TMs you need for the mep003 download the -12 tm (not the one ending in LO) and look at pdf page 53. thats the control diagram
Also for reference I wouldn't run a wire directly from the battery to whatever you're testing because you're relying on absolutely no over current protection so if you have something badly shorted to ground you're going to find out very quickly and very burny. Just something to keep in mind
I've never seen a pump clog cause the circuit breaker trip. That is a classic sign of capacitor failure.
Do this for me so I make sure that we're on the same page unplug the fuel pumps from the generator place the set in run and prime and two of those pumps should have 24 volts to chassis...