It's absolutely possible.
Not to mention these are apples to oranges. Your standard household breaker is a thermo mag breaker (thermo being the slow overload trip, mag(netic) being the inrush. Their trip curve (time vs current) is rather forgiving (especially GE breakers).
Now for...
Short answer: it's normal, and holding closed is a not so good idea
Long answer:
These are momentary switches. So the return to center is normal. The way these circuits work is electrically held. Meaning when you select closed the contactor closes and electrically holds itself on...
The power in my neighborhood was so bad that a breeze would take it down. Last major outage was Irma, 9 days with no ac in september sucked. ever since investing in MEP (and a few bad legal words to the utility) the longest outage was 2 hours.
Quite simply Add load
Long answer: wetstacking can be an issue however it doesnt happen overnight. What i do is after an outage or on a periodic basis wire in a set of heaters and let it bake. If you are really concerned that it needs to happen now any heavy load appliance will do ( Bake a...
There is nothing preventing you from :
A. Turning on the generator with line power available
B. Turning the generator on during an outage with the house main in the closed position.
The only thing preventing the generator current from reaching outside of your home is a written procedure of...
You are setting yourself up for a massive injury to yourself or others. To properly feed your house you need at minimum an interlock to prevent generator current from ever leaving your home. Using the generator lugs as a feed through to power your air compressor is a big nono.
Sent from my...
I would go over everything you moved and double check connections. Then you need to see what voltage the avr is seeing
Sent from my SM-S908U using Tapatalk