  1. Scoobyshep

    MEP-003A

    If they are actually bad, yes both. Why are you running a wire from the battery to the pump? Didn't you verify power to the pump quick disconnect? These are still available, but they can be quite costly. Not to mention the odds of all 3 failing together is slim.
  2. Scoobyshep

    MEP-003A

    Yes they are
  3. Scoobyshep

    MEP-003A

    This is on a 004 (my 003 isn't close by and I'm not motivated enough to put pants on to go to it). However same fuel pump. See the metal tube bolted to the chassis? That's the cap. Hope that helps
  4. Scoobyshep

    MEP-003A

    The switch should only click once per position you move it to, from what you described with 24 volt to the pump qd and no noise indicates a pump problem. A clogged pump may click very slowly. A gummed pump won't click at all. What you are hearing with the clicks is the plunger inside...
  5. Scoobyshep

    MEP-003A

    And 56% funnier Sent from my SM-S908U using Tapatalk
  6. Scoobyshep

    MEP-003A

    If you have 24volt at the quick disconnect wother the suppression capacitor is burnt out, the pump is jammed, or the pump is burnt out. The capacitor can be removed and bypassed (see Guys comment above). The pump needs further disassembly and cleaned Or pump needs replaced The...
  7. Scoobyshep

    MEP-003A

    Find the 2 main fuel pumps (one is to fill the tank). There is a quick disconnect, unplug it and see if you have 24 volts to chassis with the switch in run. If you have power pump needs help. No power we gotta dig deeper. Sent from my SM-S908U using Tapatalk
  8. Scoobyshep

    Advice needed - new guy with MEP004A

    Know the feeling. Too many projects not enough time Sent from my SM-S908U using Tapatalk
  9. Scoobyshep

    Test running the 803 in the house.

    Means your 120 loads aren't balanced. You're close enough to not worry about it. The neutral carries the unbalanced load back to the head. Sent from my SM-S908U using Tapatalk
  10. Scoobyshep

    MEP 803 A wiring help.

    Waves from Florida Can't be too careful these days. The problem is too many people don't know the risks. Sent from my SM-S908U using Tapatalk
  11. Scoobyshep

    MEP 803 A wiring help.

    Noted, is it a safe assumption you are using it for backup use? If so you need to be sure you have a proper interlock (device preventing generator power from making to utility and vice versa)
  12. Scoobyshep

    MEP 803 A wiring help.

    Single phase 120\240. L0 is neutral. L1 a phase l3 b phase. Do you know what you're doing? Because there's a lot of ways to hook generators up wrong with very devastating results. Sent from my SM-S908U using Tapatalk
  13. Scoobyshep

    Mep004a cb1 trip caused by injector pump solenoid

    Ok. So 1 of 2 things is happening, 1 it's reading in error and tripping or something is going wide open and sending the voltage high.
  14. Scoobyshep

    Mep004a cb1 trip caused by injector pump solenoid

    Let's try something that's going to sound a bit silly, take the voltage adjust knob and rotated it's full span back and forth several times then set it to the lowest setting
  15. Scoobyshep

    Mep004a cb1 trip caused by injector pump solenoid

    Turn the voltage adjustment down and try again
  16. Scoobyshep

    Mep004a cb1 trip caused by injector pump solenoid

    In the mean time, disconnect both wires and measure the coils resistance. Then measure the resistance from each post to the chassis. I'll do the same on a known good one.
  17. Scoobyshep

    Mep004a cb1 trip caused by injector pump solenoid

    Let me check I might have a spare
  18. Scoobyshep

    Mep004a cb1 trip caused by injector pump solenoid

    It's replaceable. You can also have a weak cb
  19. Scoobyshep

    003a breaker trips when loaded

    You can get smaller vfds that are single phase output. Not sure how well that will play with a start run wound motor.