  1. Triple Jim

    #LO to #6 jumper??

    I finally took the time to look at this jumper, L0 to terminal 6, and what it does. It appears that it simply ties L0 to L1 in the single phase mode. In both the 3-phase mode and the 120/240 single phase mode, L0 is already tied to terminal 6, so the jumper does nothing in those modes. In...
  2. Triple Jim

    Just purchased MEP-002A - Rent our home - suggestions on best way to use?

    There's a sticky thread that has a lot of information that could help you. Page 3 has a good illustration of the neutral-ground bonging wire location on the 002A/003A. http://www.steelsoldiers.com/showthread.php?40290-MEP-003A-hook-up-question
  3. Triple Jim

    Just purchased MEP-002A - Rent our home - suggestions on best way to use?

    Since the house is already grounded, you won't use a ground rod, but rather connect the generator's frame to the earth ground of the house. Also the generator's bonding wire from ground to neutral should be disconnected.
  4. Triple Jim

    Mep-003a charging problem on 120/240 single phase setting

    Thank you for that! I've been unclear as to whether that jumper has to be removed when the generator is not used for 120V-only power, and I never tried to sort through the 12 wires and three configurations to figure it out.
  5. Triple Jim

    Mep-003a charging problem on 120/240 single phase setting

    As in a similar recent thread, I wonder if this is caused by the jumper added to the reconnect switch, described in the TM to eliminate a "double fault". Edit: The similar thread was also started by Wolfe, on the smokstak board: http://www.smokstak.com/forum/showthread.php?p=966295#post966295...
  6. Triple Jim

    10 KW generator question

    Here you go, Jimc: http://theoldmotor.com/?p=104744
  7. Triple Jim

    Keep the 002A or the 003A?

    That's easy to fix. :grin:
  8. Triple Jim

    Keep the 002A or the 003A?

    I assume you have the meter switch in the correct position for reading single phase when in single phase mode.
  9. Triple Jim

    Cord sizing from 003 to motor

    That could be a very good suggestion, depending on bsorcs' plans for the future. Another thought is that when it's running just the saw, the 003A's breaker is really not going to give much protection. Ideally you'd have a separate 20A breaker to the saw.
  10. Triple Jim

    MEP-003 utility outlet has no power....

    Misunderstood post, never mind.
  11. Triple Jim

    Cord sizing from 003 to motor

    From the spec you posted, it looks like the motor will draw about six amps per phase when putting out its rated power. 12/4 should be plenty. Take a look at this chart: http://www.engineeringtoolbox.com/three-phase-circuit-wiring-d_737.html
  12. Triple Jim

    using home heating oil in military diesel gensets

    Huh, the one I was talking about wasn't Christmas Eve, it was January 25th, 2000. The storm dropped a very heavy, but narrow band of snow as it went north through here. 50 miles east at lake Gaston it was only about 10". Where you are it may have been only a light snow or nothing at all. I...
  13. Triple Jim

    using home heating oil in military diesel gensets

    I was here for that one, in January of 2000. I awoke to 20" and it was still coming down. It stayed below freezing for a week. Our power was out for several days and I ran a gasoline Onan in a motor home to keep the place going. Neighbors had no well water, and came to my house to fill...
  14. Triple Jim

    NO Voltage or HZ reading on meters

    As for your question about why the charge voltage was higher with load, it was probably a function of time, rather than load. If the batteries were not fully charged initially, they would have done a pretty good job of regulating the charge voltage, since the alternator puts out only a few...
  15. Triple Jim

    mep-003a teardown and refurb

    Right Jim. I'm positive that Ike's group 24s will work fine in the coldest of weather. That's what I have in my 003A, and in past decades I've put 24s to the test a few times in other applications.
  16. Triple Jim

    wet stacking or idling my Mep-003a

    Ike, agree with all, except I've had recent horrible experience buying electronic components from eBay. Specifically, there are counterfeit parts floating around, and you can't tell until you're really counting on one and it fails. I strongly recommend paying a couple bucks more to buy it from...
  17. Triple Jim

    using home heating oil in military diesel gensets

    Hey, I live way out in the country! :-D
  18. Triple Jim

    using home heating oil in military diesel gensets

    Good advice, except the line diameter will not effect pressure difference from the tank to the pump. That is defined as the liquid density times the difference in height (head). #2 fuel oil's density is listed as 57.4 lb/ft³. Dividing by 144, you get very nearly 0.4 psi per foot of lift. If...
  19. Triple Jim

    wet stacking or idling my Mep-003a

    Yes, I understand, and I did say that I don't recommend running it under 1800 rpm because there may be reasons like reduced engine cooling, and there's no good reason to do it. I'm just saying that everything I've done to test the regulator in the 002A and 003A has proven that no extra stress...
  20. Triple Jim

    wet stacking or idling my Mep-003a

    After all my testing, it's still being said that running an 002A or 003A under speed will hurt the AC regulator? The regulator has less work to do when the engine is running under 1800 rpm in these two generators, not more. I've measured the regulator output current below 1800, at 1800, and...