  1. M

    MEP-003a won't start, really confusing

    have not tried the ether yet, hate to do that if I don't have to. The smoke is greyish white, gets a little black in it the longer i turn it over, I believe this is the excess fuel in the cylinders.
  2. M

    MEP-003a won't start, really confusing

    Yes, injectors bled, solenoid fully engaged. The generator ran after installing the new injectors, we ran it for 1/2 hour or so, went to start it the next day and it wouldn't start, pulled the glo plugs and they were fried, installed new ones but now it still won't start.
  3. M

    MEP-003a won't start, really confusing

    Ok, so we have an MEP-003a that we put ion a new high pressure fuel pump in, timed it etc. We also installed new injectors, and new glo plugs. We have verified that the injectors are spitting fuel, the unit turns over, smoke comes from the exhaust, so the fuel is getting into the cylinders...
  4. M

    Need Fuel Injectors MEP-003a Onan part number 147-0136

    Thank you Guys! Got what I needed, have a Merry Christmas!!
  5. M

    Need Fuel Injectors MEP-003a Onan part number 147-0136

    I was able to find 2 brand new ones, but I need 2 more, these seem to be in short supply, anyone know where I can find 2 either new or re manufactured? or at least like new used? any help would be greatly appreciated. And yes i have e-mailed Delks to see if they have any, along with...
  6. M

    MEP-003a installing Dynagen ES52 autostart speed sensing issues

    it does frequency sensing off the ac, and I know it sees it initially because the "engine running" light is on which also works off the speed sensing, its just acting like the ac is being briefly interrupted. I have tried 2 different ac sources in the control box, both with the same results.
  7. M

    MEP-003a installing Dynagen ES52 autostart speed sensing issues

    I have installed a Dynagen ES-52 autostart module in an MEP003a, it starts the generator fine, runs for about a minute, then shuts down saying loss of speed sensing (overspeed light blinking) has anyone run into this? does somthing change about 1 minute in ? I have the speed sensing...
  8. M

    MEP-003a Frequency Gauge

    Anyone know of a good aftermarket source for the 2.75" round frequency gauge? I have a couple of them that are dead, and I would rather buy new gauges instead of taking a chance on surplus as these gauges are sensitive and fail often. There are plenty of digital gauges out there, but i would...
  9. M

    MEP-003a Need air filter assembly, anyone know part numbers or where to get this?

    I have purchased a few units at auction, and I'm getting a few more this week, but i noticed that the air cleaner assembly is missing on 2 of the units, the bracket is still there, but the hose and housing etc. are all gone. Anyone know where I can get these? the TM's don't specify a part...