  1. C

    MEP 802A Aux Fuel Pump

    I will check the voltage. What is K19?
  2. C

    MEP 802A Aux Fuel Pump

    Day tank is empty when I am testing it. I have the owner run till the low fuel shut off happens before I work on it.
  3. C

    MEP 802A Aux Fuel Pump

    I have an 802A I am working on that will not run the Aux pump. I have replaced the aux pump float, and checked that the pump itself works. I have also replaced the little box with the circuit board in it that is inline after the float. I am running out of ideas. The gen set has an autostart...
  4. C

    MEP 802 A Noisy fuel pump / stopping

    Yes, while you replies I was looking into that. The fuel is plumbed in the aux fuel fitting, and the tank is dry. I am guessing it is a transfer pump issue or a float issue. Threw me off because I was not getting a fuel light. CF
  5. C

    MEP 802 A Noisy fuel pump / stopping

    I have an 802A installed at my girlfriends off grid place and has been running fine till today. It shut down and I went to look at it. It is plumbed to a 500 gal tank with a auto/remote start installed. I noticed that the fuel pump located on the back wall left side is very noisy. It usually...
  6. C

    MEP-802a cold weather starting

    I installed one of the 100w stick on oil pan heaters on the bottom of one up here in Alaska and it has been doing good starting. Coldest it has been this year so far was -20. Oil pan heater is stuck on bottom of oil pan and 110 extension cord to power it comes in through the output (load) wiring...
  7. C

    MEP 802A vibrates badly and shuts down with low fuel light

    OK so here are some updates. First, no more low fuel lights. Second, the generator is sitting outside, but on a platform that is built up on cribbed railroad ties with 2x6 floor joists and sheets of plywood for a floor. It is about 8x8 in size. I think that the stand he built for it is causing...
  8. C

    MEP 802A vibrates badly and shuts down with low fuel light

    If it is vibrating enough, could it foam the fuel enough to trigger the low fuel? CF
  9. C

    MEP 802A vibrates badly and shuts down with low fuel light

    Gauge. Not a lot of smoke. Unable to load it more. It is connected to an off grid power system and have it set to charge batteries at 100% and 30 amps. Well, maybe I could plug an electric heater in as well CF
  10. C

    MEP 802A vibrates badly and shuts down with low fuel light

    Running at about 70% load. CF
  11. C

    MEP 802A vibrates badly and shuts down with low fuel light

    It was running smoother. I am wondering if it getting starved for fuel? Could one of the metering pumps be going out? CF
  12. C

    MEP 802A vibrates badly and shuts down with low fuel light

    It will run for 2-8 minutes, then shut down with low fuel light. It seems to be vibrating more than normal. Any suggestions? It had new fuel filters. I may try putting new ones in. CF
  13. C

    MEP 802A keeps popping CB1 Breaker

    I like it a lot. We have two we have installed. One as a remote start, the other as an auto start that is connected to an inverter. Both are working great. Peter was very helpful with any questions during the install. CF
  14. C

    MEP 802A keeps popping CB1 Breaker

    Problem Solved. First I would like to thank everyone who offered advice and helped me with this issue. Very much appreciated. :goodjob: After a lot of messing around, and looking at things I found the problem. The wires going to the oil pressure sensor near the dead crank switch had broken...
  15. C

    MEP 802A keeps popping CB1 Breaker

    It starts out in the 2-4 range then spikes once the unit starts. I'll check the prime only level this afternoon. CF
  16. C

    MEP 802A keeps popping CB1 Breaker

    Tried again and it looks like 17-22 amps
  17. C

    MEP 802A keeps popping CB1 Breaker

    I must have mis measured that. Swapped the breaker out with another and still getting the same thing. CF
  18. C

    MEP 802A keeps popping CB1 Breaker

    Diode at CR1 I think is good. Tested out at .553 one way, and OL the other. on startup the breaker CB1 max was 5.4 amps. CF
  19. C

    MEP 802A keeps popping CB1 Breaker

    Have a meter. Peter at Inova suggested checking if Diode CR1 was good as well. I'll check those this morning. CF
  20. C

    MEP 802A keeps popping CB1 Breaker

    MEP 802A keeps popping CB1 Breaker **SOLVED** Page 2 I have a 802A that has been running fine. I installed the remote/autostart from Inova Hightech. It has run fine for a few weeks. Last night it ran for 2 hours, then died. When I checked it. CB1 was popped. If I reset CB1, it will crank...