If no power to the lugs with the contactor switch in the UP position. Then...
Here is a diagram of how the coil in K1 is powered while you have the contactor switch in the UP position.
The RED path is 24 volts to K1-X.
The Green path is ground path to K1-Y.
Check for 24 volts and ground...
OK, your test h. result of 22.7 VDC confirms my suspicion that there is an open circuit from VR terminals 5,6 and the static exciter or a burned-out static exciter. Most likely it's a wiring/continuity issue and not the static exciter.
Here is the wiring path from VR terminal 5 to F- of the...
The image you posted is not the AC VR Test in the TM. That's a brief cheat sheet without the needed steps and conditions to correctly perform the tests.
The table of voltages listed on your sheet are approximately what one would measure IF the set was running, no load and outputting correct AC...
It would ready help if you performed the AC Voltage Regulator test per the TM. It has the expected readings for each test.
The 17.4vdc reading you reported indicates to me that you have may have an open circuit between VR terminals 5,6 and the Static exciter.
If the Fuse Mod fuse is good and you don't have power the the outlet then you need to perform the AC Voltage Regulator test. Post up the readings for each test step and we'll guide you from there.
Unlike other generators the AC Voltage Regulator in the 002, 003 does not directly drive the exciter. It does it indirectly via the CVT and other components.
Here is an excellent video on how the voltage regulation system works.
YouTube Video
You may want to swap the AC VRs between the two...
The %Load meter doesn't actually display the current at the L3 lug in 120/240 mode.
The %Load meter is actually displaying the current provided by one of the 3 pairs of windings in the gen head.
In 120/240 mode the %Load will display the total load applied to L1 and L3 combined, not just L3.
The...
What I did was just a test markup to see if it's possible. Basically, it's just adding text "notes" to an existing PDF.
I don't have a way of marking up just 1 page and swapping it into other PDFs without a fancy PDF editor.
If it's just a few notes like I did in my test TM in say two TM's per...
I was able to edit a copy of an 002 -34 TM to add the info from your screenshot.
Not too difficult to do in Microsoft Edge PDF viewer and its editing tools.
Also visually check the VR board for burned components.
I've repaired a number of the VR's and besides the three transistors failing I've also found burned out resistors. Obvious charring. The diodes are prone to moisture creeping into them causing them to open up internally. If the diodes...