• Steel Soldiers now has a few new forums, read more about it at: New Munitions Forums!

  • Microsoft MSN, Live, Hotmail, Outlook email users may not be receiving emails. We are working to resolve this issue. Please add support@steelsoldiers.com to your trusted contacts.

Search results

  1. juddspaintballs

    MEP-003a No voltage

    I'll try to get to testing the transformers on Thursday when I get home. Are the T1 and T2 transformers the same between MEP-002a's and MEP-003a's in case I need to take Ray70 up on his offer?
  2. juddspaintballs

    MEP-003a No voltage

    I didn't see a procedure for testing them. I did a visual inspection of both and I couldn't find any disconnected little red wires in the transformers from the backs of the screw terminals.
  3. juddspaintballs

    MEP-003a No voltage

    Thank you for the offer, Ray. I did order a linear reactor today. If that doesn't work, I'll take you up on it.
  4. juddspaintballs

    MEP-003a No voltage

    Thank you to Triple Jim for shipping the regulator very quickly. I received it today and installed it. No luck. I'm not upset I bought a VR from him at all. It was in the future plans anyways. If I remove terminal 17 on this VR as well, voltage goes above 300 on the gauge. If I install...
  5. juddspaintballs

    MEP-003a No voltage

    Excellent! I wasn't expecting you to be done with it so soon.
  6. juddspaintballs

    MEP-003a No voltage

    Thanks, guys. I've placed an order for a new AC VR. I also placed an order for a NOS stator so I can fix my DC charging system. I'll let you know if the VR fixes things when it comes in. In the mean time, I'll check the T1 and T2 wires just to be sure.
  7. juddspaintballs

    MEP-002a and MEP-003a DC Charging System Test

    I did not. I did not realize I should do that.
  8. juddspaintballs

    MEP-003a No voltage

    I started and ran several times today. No voltage and frequency drops off shortly after starting (and flashing). Over 300v if terminal 17 is off of the VR. Are we thinking bad VR now?
  9. juddspaintballs

    MEP-002a and MEP-003a DC Charging System Test

    I know this is old. My MEP-003a has 24v DC at the red banded regulator wire with the set off. It also has the same voltage with the set on. The two leads coming from the stator read 22.52v AC between them with the set running. I pulled the blower wheel and cleaned the stator with brake...
  10. juddspaintballs

    MEP-003a No voltage

    The plot thickens. I went out and started it again. Frequency went right to 60 and remained. Voltage went over 300 on the gauge. As I walked down to the garage to get the Fluke, I heard the tone of the motor change a couple of times like it slightly loaded, and then went back to normal...
  11. juddspaintballs

    MEP-003a No voltage

    Me either
  12. juddspaintballs

    MEP-003a No voltage

    The wires were on the studs. They just didn't have anything holding them on tight.
  13. juddspaintballs

    MEP-003a No voltage

    The two with yellow ring terminals in the picture above.
  14. juddspaintballs

    MEP-003a No voltage

    I disconnected terminal 17 at the voltage regulator. I had zero volts AC at the convenience outlet or the output lugs. I closed it up to come inside to tell you guys this, assuming that meant my VR wasn't the issue. Then, I looked down and saw that I had forgotten to reconnect all of the...
  15. juddspaintballs

    MEP-003a No voltage

    Ok, thank you for that clarification. I'm waking up in 5 hours to go to work for 48 hours. I won't be home much on Sunday and I work again Monday. I'll try to find the time to do that check on Sunday.
  16. juddspaintballs

    MEP-003a No voltage

    When cranking (only), I have ~21v DC at S1 pin 27, TB4-10, A1 pins 7 and 8, and TB5-5. Prior to cranking, there is no voltage at those locations and after the generator is running, there is no longer voltage at those locations. As the motor is just starting to run, the voltage at those...
  17. juddspaintballs

    MEP-003a No voltage

    I'll figure out where TB5 is and test voltage at TB5-5 while starting. It should be easy enough to find at this point. Am I testing it as AC or DC voltage? I'm guessing AC. I'm thankful you guys can understand the wiring diagrams better than I can and know a lot more about these units...
  18. juddspaintballs

    MEP-003a No voltage

    I really don't know. I'm learning as we go here. I just want my generator working again and I'm following directions from more knowledgeable people.
  19. juddspaintballs

    MEP-003a No voltage

    "(5) Linear Reactor (Ll). Disconnect electrical connectors from control box. Use an ohmmeter to check resistance of each of the three windings in the reactor by checking resistance between terminals 1 and 2, 3 and 4, 5 and 6. Resistance for each winding must be 13.5 ohms plus or minus 1.35, if...
  20. juddspaintballs

    MEP-003a No voltage

    The manual said to disconnect the electrical connectors on the ac output box or something like that. I'm not home to reread the manual, but it made it sound like just unplug the 4 exterior connectors on the box. I tried to undo the 6 connections on the linear reactor but the wiring is so tight...