  1. Scoobyshep

    What is a good mobile set up for using my MEP 803A

    Do yourself a favor and use so cord or extention cords. Romex is a bitch to roll up Sent from my SM-G973U using Tapatalk
  2. Scoobyshep

    What is a good mobile set up for using my MEP 803A

    4 is a bit overkill, but it wont harm anything in your setup if you ground the generator make sure the neutral and ground are bonded together at the generator and only at the generator. Sent from my SM-G973U using Tapatalk
  3. Scoobyshep

    What is a good mobile set up for using my MEP 803A

    How about corner grounded delta? Sent from my SM-G973U using Tapatalk
  4. Scoobyshep

    What is a good mobile set up for using my MEP 803A

    more accurately 120 degrees out of phase vs 180 degrees out of phase Sent from my SM-G973U using Tapatalk
  5. Scoobyshep

    2 MEP803a with issues.....Overload with 8kw load on one and Bogging down on the other.

    yes. 120 single, 120/240 single or 120/208 three
  6. Scoobyshep

    What is a good mobile set up for using my MEP 803A

    They should be, usually on these sets the 120/ 240 setting is double delta and not a low open or closed delta
  7. Scoobyshep

    What is a good mobile set up for using my MEP 803A

    Thats when you have an open or closed delta winding. line to line will be 240 all around (L1-L2, L2-L3, L3-L1) and line to ground on L1 and L3 will be 120 L2 to ground will be 208. which is your high leg or wild leg. Wild leg is more commonly used with an open delta configuration as it tends...
  8. Scoobyshep

    MEP-006A Help with Low Voltage Problem

    Do You have the engine up to speed (60 HZ) where are you measuring voltage?
  9. Scoobyshep

    3.5KW runs great for 30 minutes, Dies, Wait 30 minutes, runs great for 30minutes

    Spark air or fuel, I had a gas generator do something similar, ended up being a bad coil
  10. Scoobyshep

    MEP-002a damaged by Laura

    Oh thats a shame. Hopefully You and yours fared well. Steel part or Aluminum?
  11. Scoobyshep

    New -002A Owner looking for guidance

    The advantage is in the ratings and the availability. Do yourself a favor and install a battery disconnect switch as well.
  12. Scoobyshep

    What is a good mobile set up for using my MEP 803A

    If you are not connecting this to an established service, bond the neutral to ground and drive a ground rod Sent from my SM-G973U using Tapatalk
  13. Scoobyshep

    803A Hard to start

    I really need to stop reading these posts on my phone.
  14. Scoobyshep

    MEP 002/003 Motor mounts

    My 003 with 3 of the 4 bad didnt vibrate too bad. the spacer is rubber coated .
  15. Scoobyshep

    MEP 002/003 Motor mounts

    until all #17s delaminate, and all #19s fall upon all #20s then it looks alrght, just 9/16 inch shorter
  16. Scoobyshep

    MEP 002/003 Motor mounts

    maybe this will help
  17. Scoobyshep

    MEP 002/003 Motor mounts

    Yep, Many ways to fix this.
  18. Scoobyshep

    MEP 002/003 Motor mounts

    Measured at .8765 inch. The spacer is longer but the motor mounts are conical in the inside, so the bushing is much shorter than the spacer. OD dimensions of the spacer may vary as it is coated in rubber.
  19. Scoobyshep

    MEP 002/003 Motor mounts

    It can work, the only problem that my have is getting the spacer pressed into the tubing. at 7/8 inch the spacer was still a tight fit. More than one way to defur this particular feline.