Hard to tell online. Alot of people make very bad mistakes with grounding and bonding (master electrician turned engineer here). You will need a 1 to 1 transformer to filter. Its size is determined by the output current. To prove the concept you can use a smaller transformer to test (in a pinch...
It depends if there is a switching action on your neutral if you're switching the hots only then do not bond the generator if you are switching the neutral as well then you need to bond the generator.
If you are running with a bond in the system can be at your panel if you're not switching the...
Make sure you have a healthy neutral to ground bond for starters. I've never seen it done with a generator but with motors and drives we used to use a line reactor to filter out weird harmonics.
Sent from my SM-G950U using Tapatalk
I had a similar issue with my 004. Long story short there was a burnt trace on the A5 card. It was off of the relay. Once I repaired the card it worked great. Another thing to look at is the speed switch.
Sent from my SM-G950U using Tapatalk
Ok. The first means of disconnect your neutral and ground are bonded. At this point you can land the white and green to the same place. On the generator there should be a place where the neutral and ground are bonded. That needs to be seperated.
Sent from my SM-G950U using Tapatalk
Be ready to disable brakes, they are usually air over hydraulic. Last one i messed with i deeded the Jack to get it on the pintle ring as the trailer sits high.
Sent from my SM-G950U using Tapatalk
Theres a rectifier up there thats functioning as a diode block. Personally i had one there the check valve in the pump jammed up. I had to unscrew the bottom of the pump and knock the ball loose.
Switch in run and battle short on you should hear the pumps running, fast if day is empty real...
So it never produces power? Are you following the startup instructions precisely? These units typically need to flash the field windings when starting.
Sent from my SM-G950U using Tapatalk
They are supposed to be momentary. And there are indeed no interlocks on the doors. They are designed to be used by semi competent adults.
Sent from my SM-G950U using Tapatalk
You need to get to where the wiring leaves the head, you meed to use a megaohm meter to see whats leaking. Theres a very specific process to checking a head for a bad winding.
Sent from my SM-G950U using Tapatalk
You can use a laser tach, if you are using an external meter to watch frequency that should be sufficient as hz is directly related to rpm. You dont want to run that generator too slow as it puts alot of stress on the regulator. If you can't get the rpm high enough you may need to replace a fuel...