  1. Scoobyshep

    MEP-802a House hookup

    You would be better off installing an inlet for the largest current you would be using. IE you have a generator capable of 40 amps and one capable of 60 amps. install a 60 amp inlet. Its safe to use the 60 amp generator and if needed you can plug the 40 amp in as the overcurrent protection is...
  2. Scoobyshep

    Generator Size

    unfortunately it wasnt an off the shelf device, I used an allen bradley PLC and wrote the software to fit my needs.
  3. Scoobyshep

    Generator Size

    It doesnt wetstack too badly, on occasion I use a heater I built up to load it and clear it out. Yes I have it wired up to be fully automated.
  4. Scoobyshep

    Generator Size

    I use my 004 for standby use, it is 3 phase but can be very easily rewired to single phase 120/ 240. I wired mine to autostart (but that took some doing) and 5000 seems a bit on the high side to me.
  5. Scoobyshep

    Generator Size

    Consumer generators are rated in starting watts so a 10 KW generator is more of an 8000 watt generator. The Military generators, when they say 10 kw they mean 10 kw and then some. Honestly the best answer is to take current readings and use that to figure out how big you really need.
  6. Scoobyshep

    Generator Size

    Has your 10 KW portable generator been running the things you need? Or is it just a few pennies short of a dollar?
  7. Scoobyshep

    MEP-802a House hookup

    at 15 feet and 60 amps 6/4 is sufficent.
  8. Scoobyshep

    MEP-802a House hookup

    Really it depends on what outcome you want. If it were me personally I would pick the loads that must be powered and install them into an emergency panel. That panel would be fed by a transfer switch normally fed from the house panel emergency feed from your generator. you can use a contactor...
  9. Scoobyshep

    Quad Field winding, purpose or how used MEP-802/3 series

    The basic physics is a spinning magnet in a coil generates electricity. using a fixed magnet creates a fixed voltage. so the new thing was using an electromagnet. the first use required brushes to get the dc power to the rotor to create the magnetic field. these are brushless, so the quad...
  10. Scoobyshep

    Conversion kit to run MEP-018A on LP

    The adjustment would be for fuel to air mixture. RPM must be maintained to keep the frequency right. switching between natural gas and propane would require mixture changes as they burn differently. natural gas is already piped in as a gas so you wont get the freezing or vaporizing issues...
  11. Scoobyshep

    MEP-802a House hookup

    In that case with a smaller generator and unpredictable schedules the best bet would be a small panel for critical loads fed through an automatic transfer switch.
  12. Scoobyshep

    MEP-802a House hookup

    Worst case if you arent home to shed the load the generators over current protection should prevent an overload. I have my 004 setup for autostart and transfer, and I've helped hook up several for manual control, it all depends on how far you want to take it and whos gonna be operating it. Sent...
  13. Scoobyshep

    Conversion kit to run MEP-018A on LP

    Things to keep in mind: Natural gas is like any other utility, they can be knocked out due to a disaster (we had it happen one year when a tornado blew a tree down and ripped up a gas line). Propane, can get expensive, and in an emergency can be difficult to find. I have a civ generator that...
  14. Scoobyshep

    Conversion kit to run MEP-018A on LP

    There are some kits out there to do so.
  15. Scoobyshep

    Assistance Needed: MEP-803a will run for 15 mins and quit

    I would be interested the voltage on the fuel shutdown solenoid. Sent from my SM-G950U using Tapatalk
  16. Scoobyshep

    MEP-803A just smoked the "Fuel Float Module" electrical box to right of fuel tank.

    Yes the MOSFET. They arent too many variations out there. There has to be a diagram in one of the TMs. As for what smoked it, its usually an overload or short Sent from my SM-G950U using Tapatalk
  17. Scoobyshep

    MEP-803A just smoked the "Fuel Float Module" electrical box to right of fuel tank.

    That should be an easy component to replace.
  18. Scoobyshep

    Mep 803 or 804 Generator Question

    99% of appliances that require 240 will run just fine on 208.
  19. Scoobyshep

    Mep-805a- 30kw generator