  1. DieselAddict

    Converting a MEP-831A to standard generator

    The actuator if I remember correctly can withstand a good bit more than than 11v. I'm using B+ to drive it (~27v). Since its a PWM output I just clamp the duty cycle on the PWM to limit the current. Ultimately when I'm done I may choose a less expensive driver and put in one an additional power...
  2. DieselAddict

    Converting a MEP-831A to standard generator

    Just as a general FYI, I'm using a DC Brushed motor driver to drive the actuator for the custom speed controller I've been working on. https://www.pololu.com/product/2992
  3. DieselAddict

    Converting a MEP-831A to standard generator

    Yea, in the pinned position it should be in that range. I want to say (from memory) that the mechanical governor needs to have its absolute top speed set for about 3750-3800. With that the electronic governor will be able to push it up to about 3600 without needing too much torque from the...
  4. DieselAddict

    Converting a MEP-831A to standard generator

    Lets start with some basic information. Pull start the engine without turning on the main switch. Make sure the electronic governor arm is free to move (not on the magnet and not "pinned" fully to the right). What RPM does the engine run? It should be a low idle. If it idles at 3600 rpm you...
  5. DieselAddict

    My MEP-803a experience

    Is it low on the gauge?
  6. DieselAddict

    How to hookup MEP-802A and MEP-003A through Asco transfer switch to dual 200A panels

    No worries. Thanks for the update. Looking forward to seeing the install.
  7. DieselAddict

    Opinions on MEP-831A

    My seat of the pants MTBF report is that the 831 is much less reliable than the 802s and 803s that I've worked on. Every one I've gotten from auction except one (which was brand new) has needed a repair that would have kept it from being mission ready. And yet I kept buying them. And fixing...
  8. DieselAddict

    How to hookup MEP-802A and MEP-003A through Asco transfer switch to dual 200A panels

    You're welcome. Its not my logic, it is however code. Look up NEC 702.4 and make sure you understand the rules for adding a generator utilizing an ATS. And yes, you are correct that you would need a large generator for handling a 200A service. I did make make the assumption that you were...
  9. DieselAddict

    Opinions on MEP-831A

    I didn't post about the PMA failure because it arrived to me that way from auction. One of those cases where I should have looked more closely before bidding. Luckily it wasn't a big money mistake. It had a shorted winding from overheating.
  10. DieselAddict

    Opinions on MEP-831A

    I've not had an inverter failure in one yet but I have had multiple governor module failures and one PMA failure.
  11. DieselAddict

    How to hookup MEP-802A and MEP-003A through Asco transfer switch to dual 200A panels

    It is against code to automatically connect a generator and create an overload condition on the generator. That is one of the issues with putting in an ATS. Its not just the rating of the ATS but also the rating of the generator. You can't connect a generator AUTOMATICALLY with more connected...
  12. DieselAddict

    How to hookup MEP-802A and MEP-003A through Asco transfer switch to dual 200A panels

    Just want to point out that using a 225a automatic transfer switch with a 10kw generator is against code without active load shedding on your downstream panels.
  13. DieselAddict

    MEP803A Smoke- wet stacked, rings or injectors?

    Nice job! Glad you got it cleaned out.
  14. DieselAddict

    MEP803A fuel level adjustment

    You are correct. What you have in your hand is the low fuel switch and the AUX fuel switch.
  15. DieselAddict

    MEP803A fuel level adjustment

    Yep. Sounds like you need to troubleshoot the sending unit setup. Guy pointed you in the right direction to get you started.
  16. DieselAddict

    MEP803A fuel level adjustment

    Before you do any adjustment does the gauge read the correct level?
  17. DieselAddict

    MEP803A fuel level adjustment

    The sending unit assembly adjusts up and down via a fitting on the outside top of the tank. You need to remove the end cover of the generator to get to it. Do you have the manual to reference on the fuel sending unit?
  18. DieselAddict

    Generator wet stacking discussion

    I am going to have to snag one of these to play with. :)
  19. DieselAddict

    Generator wet stacking discussion

    Here are my thoughts on wetstacking.. Strictly my opinions based on a reasonable amount of experience running/fixing MEPs and being system owner of 2MW of diesel generators at work for more than 15yrs. Without a doubt if you idle your generator for long periods you are going to cause...
  20. DieselAddict

    Generator wet stacking discussion

    If this is something that truly worries then the best thing to do is to install a EGT with a data recorder. If you accumulate too many hours of light load as will be shown on the EGT then run your dryer for an hour. The second thing you can do to minimize accumulation is to insulate the...